2.11 Undervoltage and Overvoltage Protection (optional)
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
153
2.11
Undervoltage and Overvoltage Protection (optional)
Voltage protection has the function of protecting electrical equipment against undervoltage and overvoltage.
Both operational states are unfavourable as overvoltage may cause, for example, insulation problems or und-
ervoltage may cause stability problems.
The overvoltage protection in the 7SD610 detects the phase voltages U
L1-E
, U
L2-E
and U
L3-E
, the phase-to-
phase voltages U
L1-L2
, U
L2-L3
and U
L3-L1
, as well as the displacement voltage 3U
0
. Instead of the displacement
voltage any other voltage that is connected to the fourth voltage input U
4
of the device can be detected. Fur-
thermore, the device calculates the positive sequence system voltage and the negative sequence system
voltage so that the symmetrical components are also monitored. Here compounding is also possible which cal-
culates the voltage at the remote line end.
The undervoltage protection can also use the phase voltages U
L1-E
, U
L2-E
and U
L3-E
, the phase-to-phase volt-
ages U
L1-L2
, U
L2-L3
and U
L3-L1
, as well as the positive sequence components.
These voltage protection functions can be combined according to the user's requirements. They can be
switched on or off separately, or used for alarm purposes only. In the latter case, the respective trip commands
do not appear. Each voltage protection function is dual-stage, i.e. it is provided with two threshold settings each
with the appropriate times delay.
Abnormally high voltages often occur e.g. in low loaded, long distance transmission lines, in islanded systems
when generator voltage regulation fails, or after full load shutdown of a generator with the generator discon-
nected from the system. Even if compensation reactors are used to avoid line overvoltages by compensation
of the line capacitance and thus reduction of the overvoltage, the overvoltage will endanger the insulation if the
reactors fail (e.g. due to fault clearance). The line must be de-energised within a very short time.
The undervoltage protection can be applied, for example, for disconnection or load shedding tasks in a system.
Furthermore, this protection scheme can detect impending stability problems. With induction machines under-
voltages have an effect on the stability and permissible torque thresholds.
2.11.1
Overvoltage Protection
Overvoltage Phase-to-Earth
Figure 2-56 depicts the logic diagram of the phase voltage stages. The fundamental component is numerically
filtered from each of the three measuring voltages so that harmonics or transient voltage peaks are largely elim-
inated. Two threshold stages
Uph-e>
(address
3702
) and
Uph-e>>
(address
3704
) are compared with the
voltages. If a phase voltage exceeds these thresholds, it is indicated in a phase-segregated way. Furthermore,
a general pickup indication
„Uph-e> Pickup“
and
„Uph-e>> Pickup“
is given. The drop-out to pickup
ratio can be set (
Uph-e>(>) RESET
(address
3709
)).
Every stage starts a time delay which is common to all phases. Expiry of the respective time delay
T Uph-e>
(address
3703
) or
T Uph-e>>
(address
3705
) is signalled and results in the trip command
„Uph-e>(>)
TRIP“
.
The overvoltage protection phase-to-earth can be blocked via a binary input
„>Uph-e>(>) BLK“
.
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...