2 Functions
80
7SD5 Manual
C53000-G1176-C169-1
The following modes are available:
• Log out device: logging out a device from the universal line protection system with
the circuit breaker being switched off. The differential protection continues to be
active at the other end(s); thus, the other end(s) may remain switched on. As the
local circuit breaker is open (as well as the line disconnector) revision work can be
performed at the local feeder without affecting operation at the other end(s).
This mode can be switched on or off in the following ways:
– Using the integrated keypad: Menu Control/Taggings/Set: „Logout“
– Via a binary input (No 3451
„>Logout“
), if this has been configured when allo-
cating the binary inputs
– In DIGSI with Control/Taggings: „Logout local device“
• Test mode: When this mode is activated, except for the device where the test mode
is activated, the differential protection is blocked for the entire system. All currents
from the other devices are set to zero in the local device. The local device only eval-
uates the locally measured currents but does not transmit them to the other devices;
this allows to test the device. Moreover, the test mode prevents in the local device
that tripping of the differential protection generates a transfer trip signal.
If the device has been logged out before (see „Logout“), all the other devices can
operate normally. Otherwise, the differential protection system is blocked in all
linked devices. Depending on the parameter settings, either the distance protection
assumes the entire protection function over all zones, or the time overcurrent pro-
tection becomes effective as emergency function.
This mode can be switched on or off in the following ways:
– Using the integrated keypad: Menu Control/Taggings/Set: „Test mode“
– Via a binary input (No. 3194
„>Test Diff.“
), if this has been configured when
allocating the binary inputs. In this case the existing CFC chart for Log out device
must be rearanged with the I/O's for Test mode or a new CFC chart has to be
created.
– In DIGSI with Control/Taggings: „Diff: Test mode“
• Commissioning mode: The trip commands of the differential protection system are
blocked in the commissioning mode. The differential system as an entity can be
checked using primary or secondary values; this can be done on the local display,
with DIGSI or with the WEB-Monitor. If the WEB-Monitor is used, the current oper-
ating point is marked in the differential protection characteristic.
This mode can be switched on or off in the following ways:
– Using the integrated keypad: Menu Control/Taggings/Set: „Commissioning
mode“
– Via a binary input (No. 3195
„>Comm. Diff“
), if this has been configured when
allocating the binary inputs. In this case the existing CFC chart for Log out device
must be rearanged with the I/O's for Test mode or a new CFC chart has to be
created.
– In DIGSI with Control/Taggings: „Diff: Commissioning Mode“
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...