2.1 General
55
7SD5 Manual
C53000-G1176-C169-1
2.1.3
Change Group
2.1.3.1
Purpose of the Setting Groups
Up to four independent setting groups can be created for establishing the device's
function settings. During operation, the user can locally switch between setting groups
using the operator panel, binary inputs (if so configured), the operator and service in-
terface per PC, or via the system interface. For reasons of safety it is not possible to
change between setting groups during a power system fault.
A setting group includes the setting values for all functions that have been selected as
Enabled
during configuration (see Section 2.1.1.3). In 7SD5 devices, four indepen-
dent setting groups (A to D) are available. Whereas setting values and options may
vary, the selected scope of functions is the same for all groups.
Setting groups enable the user to save the corresponding settings for each applica-
tion. When they are needed, settings may be loaded quickly. All setting groups are
stored in the relay. Only one setting group may be active at a given time.
2.1.3.2
Setting Notes
General
If multiple setting groups are not required. Group A is the default selection. Then, the
rest of this section is not applicable.
If multiple setting groups are desired, the setting group change option must be set to
Grp Chge OPTION
=
Enabled
in the relay configuration of the functional scope
(Section 2.1.1.3, address
103
). For the setting of the function parameters, you can
configure each of the required setting groups A to D, one after the other. A maximum
of 4 is possible. To find out how to proceed, how to copy and to reset settings groups,
and how to switch between setting groups during operation, please refer to the
SIPROTEC
®
4 System Description.
Two binary inputs enable changing between the 4 setting groups from an external
source.
251
K_ALF/K_ALF_N
1.00 .. 10.00
1.00
k_alf/k_alf nominal
253
E% ALF/ALF_N
0.5 .. 50.0 %
5.0 %
CT Error in % at k_alf/k_alf
nominal
254
E% K_ALF_N
0.5 .. 50.0 %
15.0 %
CT Error in % at k_alf nominal
Addr.
Parameter
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...