System Power Swing (with impedance) (optional)
Power swing detection
Rate of the impedance vector and observation of the path
curve
Maximum power swing frequency
Approx. 7 Hz
Power swing blocking programs
Block 1st zone only
Block higher zones
Block 1st and 2nd zone
Block all zones
Power swing trip
Trip following instable power swings
(out-of-step)
Trip time delay after power swing block
0.08 to 5.00 s
Increments 0.01 s