3 Mounting and Commissioning
478
7SD5 Manual
C53000-G1176-C169-1
WARNING!
Warning of dangers evolving from improper primary tests
Non-observance of the following measure can result in death, personal injury or sub-
stantial property damage.
Primary tests may only be carried out by qualified persons who are familiar with com-
missioning protection systems, with managing power systems and the relevant safety
rules and guidelines (switching, earthing etc.).
3.3.1
Test Mode / Transmission Block
Activation and
Deactivation
If the device is connected to a central control system or a server via the SCADA inter-
face, then the information that is transmitted can be modified with some of the proto-
cols available (see Table „Protocol-dependent functions“ in the Appendix A.5).
If
Test mode
is set ON, then a message sent by a SIPROTEC
®
4 device to the main
control system has an additional test bit. This bit allows the message to be recognized
as resulting from testing and not an actual fault or power system event. Furthermore,
it can be determined by activating the
Transmission block
that no annunciations at
all are transmitted via the system interface during a test mode.
The SIPROTEC
®
4 System Description describes how to activate and deactivate test
mode and blocked data transmission. Note that when DIGSI
®
is being used, the
program must be in the
Online
operating mode for the test features to be used.
3.3.2
Checking the Time Synchronization Interface
If external time synchronization sources are used, the data of the time source (antenna
system, time generator) are checked (see Section 4 under „Time Synchronization“). A
correct function (IRIG B, DCF77) is recognized in such a way that 3 minutes after the
startup of the device the clock status is displayed as
„sychronized“
, accompanied
by the indication
„Alarm Clock OFF“
.
Table 3-14
Time status
No.
Status text
Status
1
– – – – – – – –
synchronized
2
– – – – – – ST
3
– – – – ER – –
not synchronized
4
– – – – ER ST
5
– – NS ER – –
6
– – NS – – – –
Legend:
– – NS – – – –
– – – – ER – –
– – – – – – ST
time invalid
time fault
summertime
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...