2.23 Function Control and Circuit Breaker Test
411
7SD5 Manual
C53000-G1176-C169-1
2.23.3 Device
The device requires some general information. This may be, for example, the type of
indication to be issued in the event a power system fault occurs.
2.23.3.1 Trip-dependent Messages
The indication of messages masked to local LEDs, and the maintenance of spontane-
ous messages, can be made dependent on whether the device has issued a trip
signal. This information is not output if one or more protection functions have picked
up due to a fault, but the 7SD5 has not initiated the tripping because the fault was
cleared by another device (e.g. on another line). These messages are then limited to
faults on the protected line.
The following figure illustrates the creation of the reset command for stored messages.
When the relay drops off, stationary conditions (fault display Target on PU / Target on
TRIP; Trip / No Trip) decide whether the new fault will be stored or reset.
Figure 2-183
Creation of the reset command for the latched LED and LCD messages
2.23.3.2 Spontaneous Indications on the Display
You can determine whether or not the most important data of a fault event is displayed
automatically after the fault has occurred (see also „Fault indications“ in Section 2.24.2
„Ancillary Functions“).
2.23.3.3 Switching Statistics
The number of trips caused by the device 7SD5 is counted. If the device is capable of
single-pole tripping, a separate counter for each circuit breaker pole is provided.
Following each trip command the device registers the value of each current phase that
was switched off in each pole. This information is then provided in the trip log and sum-
mated in a register. The maximum interrupted current is stored as well.
If the device is equipped with the integrated automatic reclosure, the automatic close
commands are also counted, separately for reclosure after single-pole tripping, after
three-pole tripping as well as separately for the first reclosure cycle and other reclo-
sure cycles.
The counter and memory levels are secured against loss of auxiliary voltage. They can
be set to zero or to any other initial value. For more details, refer to the SIPROTEC
®
4 System Description.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...