2.23 Function Control and Circuit Breaker Test
399
7SD5 Manual
C53000-G1176-C169-1
Figure 2-175
Generation of the energization signal
The line energization detection enables the distance protection, earth fault protection,
time-overcurrent protection and high-current switch onto fault protection to trip without
delay after energization of their line was detected.
Depending on the configuration of the distance protection, an undelayed trip
command can be generated after energization for each pickup or for pickup in zone
Z1B. The stages of the earth fault protection and of the time-overcurrent protection to-
gether generate an undelayed TRIP command if this was provided for in the configu-
ration. The switch onto fault protection is released phase-selectively and three-pole in
case of manual closure after energization detection. In order to generate as quickly as
possible a trip command after an energization, the fast switch-on-to-fault protection is
released selectively for each phase already when the line is open.
In order to avoid that an energization is detected mistakenly, the state „line open“,
which precedes any energization, must apply for at least 250 ms.
2.23.1.2 Detection of the Circuit Breaker Position
For Protection
Purposes
Information regarding the circuit breaker position is required by various protection and
supplementary functions to ensure their optimal functionality. This is, for example, of
assistance for
• The echo function in conjunction with the distance protection with teleprotection
(refer to Section 2.7),
• The echo function in conjunction with directional earth fault comparison scheme
(refer to Section 2.9),
• Weak infeed tripping (refer to Section 2.10.1),
• The high-current instantaneous tripping (refer to Section2.13),
• The circuit breaker failure protection (refer to Section 2.20),
• Verification of the dropout condition for the trip command (see Section „Terminating
the Trip Signal“).
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...