2 Functions
376
7SD5 Manual
C53000-G1176-C169-1
Warning Tempera-
ture Levels
By setting a thermal alarm stage
Θ
ALARM
(address
4204
) an alarm can be provided
before the tripping temperature is reached, so that a trip can be avoided by preventive
load reduction or by switching over. The percentage is referred to the tripping temper-
ature rise.
The current overload alarm setpoint
I ALARM
(address
4205
) is stated as a factor of
the nominal device current and should be set equal to or slightly below the permissible
continuous current k ·
I
N
. It can also be used instead of the thermal alarm stage. In this
case, the thermal alarm stage is set to 100 % and thus practically ineffective.
Calculating the
Overtemperature
The thermal replica is calculated individually for each phase. Address
4206
CALC.
METHOD
decides whether the highest of the three calculated temperatures (
Θ
max
) or
their arithmetic average (
Average
Θ
) or the temperature calculated from the phase
with maximum current (
Θ
at Imax
) should be decisive for the thermal alarm and trip-
ping stage.
Since an overload usually occurs in a balanced way, this setting is of minor impor-
tance. If unbalanced overloads are to be expected, however, these options lead to dif-
ferent results.
Averaging should only be used if a rapid thermal equilibrium is possible in the protect-
ed object, e.g. with belted cables. If the three phases are, however, more or less ther-
mally isolated (e.g. single conductor cables or overhead lines), one of the maximum
settings should be chosen at any rate.
2.21.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.21.4 Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
4201
Ther. OVERLOAD
OFF
ON
Alarm Only
OFF
Thermal overload protec-
tion
4202
K-FACTOR
0.10 .. 4.00
1.10
K-Factor
4203
TIME CONSTANT
1.0 .. 999.9 min
100.0 min
Time Constant
4204
Θ
ALARM
50 .. 100 %
90 %
Thermal Alarm Stage
4205
I ALARM
1A
0.10 .. 4.00 A
1.00 A
Current Overload Alarm
Setpoint
5A
0.50 .. 20.00 A
5.00 A
4206
CALC. METHOD
Θ
max
Average
Θ
Θ
at Imax
Θ
max
Method of Acquiring Tem-
perature
No.
Information
Type of In-
formation
Comments
1503
>BLK ThOverload
SP
>BLOCK Thermal Overload Protection
1511
Th.Overload OFF
OUT
Thermal Overload Protection OFF
1512
Th.Overload BLK
OUT
Thermal Overload Protection BLOCKED
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...