2 Functions
356
7SD5 Manual
C53000-G1176-C169-1
If double-ended fault locating is not desired, set address
3807
two ended
=
OFF
. The
default setting is
ON
.
If the fault location is required to be output as BCD-code, set the maximum time period
the data should be available at the outputs using address
3811
Tmax OUTPUT BCD
.
If a new fault occurs, the data are terminated immediately even when it occurs before
this time has expired. Allocate the corresponding output relays as stored if a longer
time period is desired for the output. Once a fault occurred the data will be latched until
the memory is reset or a new fault is registered.
2.19.3 Settings
2.19.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
3802
START
Pickup
TRIP
Pickup
Start fault locator with
3805
Paral.Line Comp
NO
YES
YES
Mutual coupling parall.line com-
pensation
3806
Load Compensat.
NO
YES
NO
Load Compensation
3807
two ended
ON
OFF
ON
two ended faulr location
3811
Tmax OUTPUT BCD
0.10 .. 180.00 sec
0.30 sec
Maximum output time via BCD
No.
Information
Type of In-
formation
Comments
1111
FL active
OUT
Fault locator active
1113
quality=
VI
Quality of the fault location
1114
Rpri =
VI
Flt Locator: primary RESISTANCE
1115
Xpri =
VI
Flt Locator: primary REACTANCE
1117
Rsec =
VI
Flt Locator: secondary RESISTANCE
1118
Xsec =
VI
Flt Locator: secondary REACTANCE
1119
dist =
VI
Flt Locator: Distance to fault
1120
d[%] =
VI
Flt Locator: Distance [%] to fault
1122
dist =
VI
Flt Locator: Distance to fault
1123
FL Loop L1E
OUT_Ev
Fault Locator Loop L1E
1124
FL Loop L2E
OUT_Ev
Fault Locator Loop L2E
1125
FL Loop L3E
OUT_Ev
Fault Locator Loop L3E
1126
FL Loop L1L2
OUT_Ev
Fault Locator Loop L1L2
1127
FL Loop L2L3
OUT_Ev
Fault Locator Loop L2L3
1128
FL Loop L3L1
OUT_Ev
Fault Locator Loop L3L1
1131
RFpri=
VI
Flt Locator: primary FAULT RESISTANCE
1132
Flt.Loc.invalid
OUT
Fault location invalid
1133
Flt.Loc.ErrorK0
OUT
Fault locator setting error K0,angle(K0)
1134
two ended FO
OUT_Ev
Two ended fault location
1135
Rpri single. =
VI
R (primary, single ended)
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...