2.10 Weak-infeed Tripping (optional)
257
7SD5 Manual
C53000-G1176-C169-1
Moreover, the phase-selective block signals
BLOCK Weak Inf
affect the non-delayed
logic. Faulty pickups are thus prevented, especially after the dedicated line end was
shut down.
In address
2530
WI non delayed
the stage for instantaneous tripping is switched
OFF
or
ON
continuously.
Trip with Delay
The operation of the delayed tripping is determined by three parameters:
• Address
2517
1pol. Trip
enables a single-pole trip command in case of single-
pole faults if set to
ON
.
• If set to
ON
, address
2518
1pol. with 3I0
allows a single-pole trip command
only if the threshold
3I0> Threshold
for the zero current has been exceeded. If
the threshold
3I0> Threshold
is not exceeded, single-pole faults do not lead to
tripping. Position
OFF
allows a single-pole trip command even when
3I0>
Threshold
is not exceeded. The time delay for the signal „3I0> exceeded“ is set
at address
2513
T 3I0> Ext.
.
• If set to
ON
, address
2519
3pol. Trip
allows also a three-pole trip command in
the event of a multi-pole pickup. In position
OFF
the multi-pole pickup is only report-
ed but a three-pole trip command is not issued (only report). But a single-pole or
three-pole trip command can nevertheless be issued.
A delayed tripping stage is implemented to allow tripping the dedicated line end in
case the transmission channel is faulted. When undervoltage conditions have been
detected, this stage picks up in one or more phases and after a configured time (ad-
dress
2515
TM
and address
2516
TT
) has elapsed it trips without delay.
Address
2531
WI delayed
allows to set delayed tripping as operating mode. With
ON
this stage is permanently active. With the setting
by receive fail
, this stage
will only be active if
„>WI rec. OK“
is
not
reported OFF.
To avoid spurious pickup, phase selection via undervoltage is blocked entirely in the
event of voltage failure (pickup of the fuse failure monitor or of the VT mcb). Moreover,
the corresponding phases are equally blocked if another protection function, capable
to detect faults, picks up.
2.10.3 Weak Infeed Tripping (optional)
2.10.3.1 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2501
FCT Weak Infeed
OFF
ECHO only
ECHO and TRIP
ECHO only
Weak Infeed function is
2502A
Trip/Echo DELAY
0.00 .. 30.00 sec
0.04 sec
Trip / Echo Delay after
carrier receipt
2503A
Trip EXTENSION
0.00 .. 30.00 sec
0.05 sec
Trip Extension / Echo
Impulse time
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...