2 Functions
156
7SD5 Manual
C53000-G1176-C169-1
Figure 2-53
Phasor diagram of the MHO characteristic measured values
For each distance zone an MHO characteristic can be defined by means of the param-
eter Z
r
. For each zone it may also be determined whether it operates
forwards
or
re-
verse
. In reverse direction the MHO characteristic is mirrored in the origin of the co-
ordinate system. As soon as the fault impedance of any loop is confidently measured
inside the MHO characteristic of a distance zone, the affected loop is designated as
„picked up“. The loop information is also converted to phase segregated information.
Further conditions for the pickup of a zone is that the zone may not be blocked by the
power swing blocking. Furthermore the distance protection may not be blocked or
switched off completely. Figure 2-54 shows these conditions.
The zones and phases of such a valid pickup, e.g. „Dis. Z1 L1“ for zone Z1 and phase
L1 are processed by the zone logic and the supplementary functions (e.g. teleprotec-
tion logic).
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...