Appendix
A.8 Settings
SIPROTEC, 7SC805, Manual
C53000-G1140-C380-1, Release date 05.2014
141
A.8
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
104
OSC. FAULT REC.
Device Configuration
Disabled
Enabled
Disabled
Oscillographic Fault Records
357
SMV-Stop
Device Configuration
Yes
No
No
SMV-Stop
369
VT Con Type
Device Configuration
Conventional
Cap. Volt.Meas.
Conventional
Voltage Connection type
459
SysConMUConf
Device Configuration
Disabled
Enabled
Enabled
MU Configuration via IEC61850
Configurator
461
PhaseIndepRatio
Device Configuration
Disabled
Enabled
Disabled
Phase Independent Ratio
202
Vnom PRIMARY
P.System Data 1
0.10 .. 800.00 kV
20.00 kV
Rated Primary Voltage
203
Vnom SECONDARY
P.System Data 1
34 .. 400 V
100 V
Rated Secondary Voltage (L-L)
204
CT PRIMARY
P.System Data 1
10 .. 50000 A
400 A
CT Rated Primary Current
205
CT SECONDARY
P.System Data 1
1A
5A
1A
CT Rated Secondary Current
214
Rated Frequency
P.System Data 1
50 Hz
60 Hz
50 Hz
Rated Frequency
217
Ignd-CT PRIM
P.System Data 1
1 .. 50000 A
400 A
Ignd-CT rated primary current
218
Ignd-CT SEC
P.System Data 1
1A
5A
1A
Ignd-CT rated secondary current
325
Vnom sec Vx
P.System Data 1
34 .. 230 V
100 V
Rated Secondary Voltage Vx
333
Vnom prim Vx
P.System Data 1
0.10 .. 800.00 kV
20.00 kV
Rated Primary Voltage Vx
352
U4 inverting
P.System Data 1
YES
NO
NO
U4 inverting
403
MAX. LENGTH
Osc. Fault Rec.
0.30 .. 6.00 sec
2.00 sec
Max. length of a Waveform
Capture Record
404
PRE. TRIG. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.25 sec
Captured Waveform Prior to
Trigger
405
POST REC. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
406
BinIn CAPT.TIME
Osc. Fault Rec.
0.10 .. 5.00 sec;
0.50 sec
Capture Time via Binary Input
407
VLAN ID
Merging Unit
0...4095
1
VLAN ID
408
VLAN Priority
Merging Unit
1...7
4
VLAN Priority
438
PPS Delay
Merging Unit
0
μ
s, 0.1
μ
s...5000.00
μ
s
0.0
μ
s
PPS Delay
460
PPS Synchro
Merging Unit
On
OFF
ON
PPS Synchronization
440A
Overflo Quality
Merging Unit
False
False
Quality bit: Overflow
441A
OutRang Quality
Merging Unit
Set By MU
True
False
Set By MU
Quality bit: OutofRange
(Options True and False for test
purpose)
442A
BadRef Quality
Merging Unit
False
False
Quality bit: BadReference
443A
Oscill Quality
Merging Unit
False
False
Quality bit: Oscillatory
444A
Failure Quality
Merging Unit
Set By MU
True
False
Set By MU
Quality bit: Failure
(Options True and False for test
purpose)
445A
OldData Quality
Merging Unit
False
False
Quality bit: OldData
446A
Inconsi Quality
Merging Unit
False
False
Quality bit: Inconsistent
447A
Inaccu Quality
Merging Unit
Set By MU
True
False
Set By MU
Quality bit: Inaccurate
(Options True and False for test
purpose)
448A
Test Quality
Merging Unit
Set By MU
True
False
Set By MU
Quality bit: Test
(Options True and False for test
purpose)
449A
OpeBloc Quality
Merging Unit
False
False
Quality bit: OperatorBlocked
Содержание SIPROTEC 7SC805
Страница 8: ...Preface SIPROTEC 7SC805 Manual C53000 G1140 C380 1 Release date 05 2014 8 ...
Страница 18: ...Introduction 1 3 Characteristics SIPROTEC 7SC805 Manual C53000 G1140 C380 1 Release date 05 2014 18 ...
Страница 70: ...Functions 2 5 Device Operation SIPROTEC 7SC805 Manual C53000 G1140 C380 1 Release date 05 2014 70 ...
Страница 150: ...Literature SIPROTEC 7SC805 Manual C53000 G1140 C380 1 Release date 05 2014 150 ...