Distance Protection Teleprotection Schemes
Mode
For two line ends
with one channel for each direction or
with three channels for each direction
(for phase segregated transmission)
For three line ends
with one channel for each direction and
oposite line end
Underreach
schemes
Method
Permissive Underreach Transfer Trip
(PUTT) (with overreaching zone Z1B)
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Overreach
schemes
Methods
Permissive Overreach Transfer Trip
(POTT) (with overreaching zone Z1B)
Unblocking (with overreaching zone Z1B)
Blocking (with overreaching zone Z1B)
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo impulse duration
0.00 s to 30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times.