2.6 Threshold-Switch
49
6MD665 Manual
C53000-G1876-C103-3
2.6
Threshold-Switch
Using the Threshold switch function, you can set transmission thresholds and allocate
the threshold switches to individual or multiple measured values.
2.6.1
Description
The threshold value procedure consists of the Transmission threshold configuration
dialog and the threshold switch.
Transmission
threshold
The transmission threshold determines the transmission frequency of measured
values. It is specified in percentage. If zero is selected as the threshold value for the
transmission threshold, each measured value will be transmitted to the higher-level
station. A threshold value not equal to zero results in all changes to new measured
values being added compared to the last measured value transmitted. If the sum of
the changes reaches the set percentage, a new measured value is transmitted at the
next possible point in time.
Perform the settings in the DIGSI
®
configuration matrix. You can set the central thresh-
old, configured threshold and switching object in the object properties of the mea-
sured value, tab Transmission threshold.
• Use central threshold (10%): Select this check box to use the factory-preset
threshold value of 10 %. This de-activates all the other input and output options in
this tab.
• Parameterised threshold: Set the desired value in this rotating box. The set value
multiplied by 0.1 % results in the threshold value.
• Switching object: A changeover from the central and the parameterised threshold
can be initiated by the status of a message. From the drop-down menu, select the
indication whose status shall initiate a changeover.
Threshold switch
The group Software switch (in the DIGSI
®
configuration matrix) contains all potential
switching objects. Threshold 1 is the preset value.
You can add additional thresholds (single point indications) from the information cata-
log. Assign the threshold value switch to one or several measured values via the
Switching object setting in the measured-value object properties.
2.6.2
Information
No.
Message
Type of Information
Description
-
ThreshVal1
IE
Threshold Value 1
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...