2 Functions
40
6MD665 Manual
C53000-G1876-C103-3
ary input voltage on the device exceeds 120 V
eff
. The rated value of the frequency is
taken from
3RZHU6\VWHP'DWD
.
Routing of the measurement inputs to the respective measured value channels Phase
currents and Phase voltages and the routing of the measuring results is performed
with DIGSI
®
. The direction of rotation can be changed by exchanging the phases.
Enter the display factors for the primary values for each required output when routing
the results. In this context, it must be observed that the phase-to-phase value is indi-
cated for the phase-ground voltages if the phase-to-phase voltage (rated voltage) was
set as primary value.
Specifications for secondary transformer current and secondary transformer voltage
are made in the properties dialog box of
083B
. The phase-to-phase voltage is used
as the value for the secondary transformer voltage.
2.4.7.2
Configuration Notes
6HF9ROWJ1RP9DO
The factory-preset rated transformer voltage can be set in the predefined range.
6HF&XUU1RP9DO
The secondary factory-preset rated transformer current can be set in the predefined
range.
2.4.7.3
Settings
2.4.7.4
Information
Addr.
Parameter
Setting Options
Default Setting
Description
0
SecVoltgNomVal
0.00 .. 200.00 V; <
> 0
100.00 V
Secondary Voltage Nominal
Value
0
SecCurrNomVal
0.00 .. 5.00 A; < >
0
1.00 A
Secondary Current Nominal
Value
No.
Message
Type of Information
Description
-
3P1InputU1
MK
3P1 Voltage Input U1
-
3P1InputU2
MK
3P1 Voltage Input U2
-
3P1InputU3
MK
3P1 Voltage Input U3
-
3P1InputI1
MK
3P1 Current Input I1
-
3P1InputI2
MK
3P1 Current Input I2
-
3P1InputI3
MK
3P1 Current Input I3
-
3P1_U0
MW
3P1 Zero Sequence Voltage
-
3P1_U1
MW
3P1 Phase to Earth Voltage U1
-
3P1_U2
MW
3P1 Phase to Earth Voltage U2
-
3P1_U3
MW
3P1 Phase to Earth Voltage U3
-
3P1_U12
MW
3P1 Phase to Phase Voltage U12
-
3P1_U23
MW
3P1 Phase to Phase Voltage U23
-
3P1_U31
MW
3P1 Phase to Phase Voltage U31
-
3P1_I0
MW
3P1 Zero Sequence Current
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...