4 Technical Data
136
6MD665 Manual
C53000-G1876-C103-3
Humidity
4.1.8
Service Conditions
4.1.9
Construction
Limiting temperatures for storage
–13
°
F to +131
°
F (–25
°
C to +55
°
C)
Limit temperatures during transport
–13
°
F to +158
°
F (–25
°
C to +70
°
C)
Storage and transport of the device with factory packaging!
Limiting temperatures for normal operation
(i.e. output relays not energized)
–4
°
F to +158
°
F (–20
°
C to +70
°
C)
Limiting temperatures with maximum load
(max. cont. permissible input and output
quantities)
–23
°
F to +104
°
F (–5
°
C to +40
°
C)
Permissible humidity
Mean value per year
≤
75 % relative humidity; on
56 days of the year up to 93 % relative humidity;
condensation must be avoided!
Siemens recommends that all devices be installed such that they are not exposed to direct sun-
light, nor subject to large fluctuations in temperature that may cause condensation to occur.
The protective device is designed for use in an industrial environment and an electrical utility
environment. Proper installation procedures should be followed to ensure electromagnetic
compatibility (EMC).
In addition, the following is recommended:
• All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the
numerical protective device should, as a rule, be equipped with suitable surge suppression
components.
• For substations with operating voltages of 100 kV and above, all external cables should be
shielded with a conductive shield grounded at both ends. For substations with lower oper-
ating voltages, no special measures are normally required.
• Do not withdraw or insert individual modules or boards while the protective device is ener-
gized. In withdrawn condition, some components are electrostatically endangered; during
handling the EEC standards (standards for Electrostatically Endangered Components) must
be observed. They are not endangered when inserted into the case.
Housing
7XP20
Dimensions
see dimensional
drawings, Section
4.8
Weight (maximum number of components ) approx.
6MD665 in flush mounted housing, with no measured values
12.13 lb (5.5 kg)
6MD665 in flush mounted housing, with measured values
14.33 lb (6.5 kg)
6MD665 in housing for detached operator panel, with no measured
values
15.43 lb (7 kg)
6MD665 in housing for detached operator panel, with measured values 17.64 lb (8 kg)
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...