![Siemens SIPROTEC 5 6MU85 Скачать руководство пользователя страница 84](http://html.mh-extra.com/html/siemens/siprotec-5-6mu85/siprotec-5-6mu85_manual_1266039084.webp)
Temperature Supervision
Setting Values
Pickup value
-50 °C to 250 °C
-58 °F to 482 °F
Increments of 1°C
Increments of 1°F
Time delay
0 s to 60 s
or ∞
Increments of 1 s
Dropout
Dropout differential
3 °C or 6 °F
Tolerances
Tripping delay
±1 % of the setting value or ±10 ms
Measured temperature value
±0.5 % of the setting value or ±1 °C or ±2 °F
12.25
Technical Data
12.25 Temperature Supervision
SIPROTEC 5, Merging Unit 6MU85, Manual
861
C53000-G5040-C074-1, Edition 01.2020