Addr.
Parameter
C
Setting Options
Default Setting
Comments
4207A
Kτ-FACTOR
1.0 .. 10.0
1.0
Kt-FACTOR when motor
stops
4208A
T EMERGENCY
10 .. 15000 sec
100 sec
Emergency time
4209
49 TEMP. RISE I
40 .. 200 °C
100 °C
49 Temperature rise at
rated sec. curr.
4210
49 TEMP. RISE I
104 .. 392 °F
212 °F
49 Temperature rise at
rated sec. curr.
4211
TEMPSENSOR RTD
1 .. 6
1
Temperature sensor
connected to RTD
4212
TEMPSENSOR RTD
1 .. 12
1
Temperature sensor
connected to RTD
Information List
No.
Information
Type of
Informa-
tion
Comments
1503
>BLOCK 49 O/L
SP
>BLOCK 49 Overload Protection
1507
>EmergencyStart
SP
>Emergency start of motors
1511
49 O / L OFF
OUT
49 Overload Protection is OFF
1512
49 O/L BLOCK
OUT
49 Overload Protection is BLOCKED
1513
49 O/L ACTIVE
OUT
49 Overload Protection is ACTIVE
1515
49 O/L I Alarm
OUT
49 Overload Current Alarm (I alarm)
1516
49 O/L Θ Alarm
OUT
49 Overload Alarm! Near Thermal Trip
1517
49 Winding O/L
OUT
49 Winding Overload
1521
49 Th O/L TRIP
OUT
49 Thermal Overload TRIP
1580
>RES 49 Image
SP
>49 Reset of Thermal Overload Image
1581
49 Image res.
OUT
49 Thermal Overload Image reset
2.11.4
Functions
2.11 Thermal Overload Protection 49
SIPROTEC 4, 7SJ62/64, Manual
179
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...