Addr.
Parameter
Setting Options
Default Setting
Comments
201
CT Starpoint
towards Line
towards Busbar
towards Line
CT Starpoint
203
Unom PRIMARY
1.0 .. 1200.0 kV
400.0 kV
Rated Primary Voltage
204
Unom SECONDARY
80 .. 125 V
100 V
Rated Secondary Voltage (Ph-Ph)
205
CT PRIMARY
10 .. 5000 A
1000 A
CT Rated Primary Current
206
CT SECONDARY
1A
5A
1A
CT Rated Secondary Current
207
SystemStarpoint
Solid Earthed
Peterson-Coil
Isolated
Solid Earthed
System Starpoint is
210
U4 transformer
Not connected
Udelta transf.
Usy2 transf.
Ux transformer
Not connected
U4 voltage transformer is
211
Uph / Udelta
0.10 .. 9.99
1.73
Matching ratio Phase-VT To Open-
Delta-VT
212
Usy2 connection
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-L2
VT connection for Usy2
214A
φ Usy2-Usy1
0 .. 360 °
0 °
Angle adjustment Usy2-Usy1
215
Usy1/Usy2 ratio
0.50 .. 2.00
1.00
Matching ratio Usy1 / Usy2
220
I4 transformer
Not connected
In prot. line
In prot. line
I4 current transformer is
221
I4/Iph CT
0.010 .. 5.000
1.000
Matching ratio I4/Iph for CT's
230
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
235
PHASE SEQ.
L1 L2 L3
L1 L3 L2
L1 L2 L3
Phase Sequence
239
T-CB close
0.01 .. 0.60 sec
0.06 sec
Closing (operating) time of CB
240A
TMin TRIP CMD
0.02 .. 30.00 sec
0.10 sec
Minimum TRIP Command Duration
241A
TMax CLOSE CMD
0.01 .. 30.00 sec
0.10 sec
Maximum Close Command Dura-
tion
242
T-CBtest-dead
0.00 .. 30.00 sec
0.10 sec
Dead Time for CB test-autoreclo-
sure
Change Group
Purpose of the Setting Groups
Up to four different setting groups can be created for establishing the device's function settings. During opera-
tion, the user can locally switch between setting groups using the operator panel, binary inputs (if so config-
ured), the operator and service interface from a personal computer or via the system interface. For reasons of
safety, it is not possible to change between setting groups during a power system fault.
A setting group includes the setting values for all functions that have been selected during configuration as
Enabled
or an other active option. In 7VK61devices, four independent setting groups (A to D) are available.
Whereas setting values and options may vary, the selected scope of functions is the same for all groups.
2.1.4
2.1.4.1
Functions
2.1 General
36
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...