Figure 3-8
Input/output module C-I/O-2 up to release 7VK61.../DD, with representation of the jumper
settings required for checking the configuration settings
Table 3-10
Jumper setting for the contact mode of binary output BO6
Jumper
Normally-open contact (NO)
Closed in quiescent state (NC)
Factory setting
X41
1-2
2-3
1-2
The nominal current of the current input transformers are checked on the input/output board C-I/O-2. All
jumpers must be set for one nominal current, i.e. one jumper (X61 to X64) for each input transformer and
additionally the common jumper X60. The position of jumper X64 is not relevant.
Jumpers X71, X72 and X73 on the input/output board C-I/O-2 are used for setting the bus address and must
not be changed. The following Table lists the jumper presettings.
Table 3-11
Jumper settings of the module address of the input/output module C-I/O-2
Jumper
Mounting location
X71
1-2 (H)
X72
1-2 (H)
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7VK61, Manual
191
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...