[prinzip-ausloesekrueb-2-be-wlk-010802, 1, en_US]
Figure 2-73
Principle of the trip circuit monitoring with two binary inputs
RTC
Relay trip contact
52
Circuit breaker
52TC
Circuit-breaker trip coil
52a
Circuit-breaker auxiliary contact (NO contact)
52b
Circuit-breaker auxiliary contact (NC contact)
V-Ctrl
Control Voltage (tripping voltage)
V-BI1
Input voltage for first binary input
V-BI2
Input voltage for second binary input
Monitoring with two binary inputs does not only detect interruptions in the trip circuit and loss of control
voltage, it also monitors the response of the circuit breaker using the position of the circuit-breaker auxiliary
contacts.
Depending on the conditions of the trip contact and the circuit breaker, the binary inputs are activated (logical
condition “H” in the following table), or faulted (logical condition “L”).
A state in which both binary inputs are not activated (“L”) is only possible in intact trip circuits for a short tran-
sition period (trip relay contact closed but circuit breaker not yet open).
A continuous state of this condition is only possible when the trip circuit has been interrupted, a fault exists in
the trip circuit, a loss of battery voltage occurs, or malfunctions occur with the circuit-breaker mechanism.
Therefore, it is used as monitoring criterion.
Table 2-5
Condition Table for Binary Inputs, Depending on RTC and CB Position
No
.
Command relay
Circuit breaker
52a contact 52b contact BI 1 BI 2 Dynamic state Static state
1
Open
EIN
Closed
Open
H
L
Normal operation with circuit
breaker closed
2
Open
AUS
Open
Closed
H
H
Normal operation with circuit
breaker open
3
Closed
EIN
Closed
Open
L
L
Transition or
disturbance
Disturbance
4
Closed
AUS
Open
Closed
L
H
The command relay has success-
fully activated the circuit breaker
Functions
2.14 Monitoring Functions
SIPROTEC 4, 7SD80, Manual
163
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...