SIPLUS HCS3200
Operating Instructions, 07/2014, A5E31278506C/002
21
Mounting
5
5.1
Preparations
The HCS3200 device can be mounted either on a wall or in a steel frame.
NOTICE
The temperature of the cooling fins can reach 80 °C
When mounting the device on a wall, ensure that the wall is designed to withstand
temperatures up to around 80 °C.
Minimum clearances
Maintain the following minimum clearances from other devices:
Figure 5-1
Clearances for mounting an HCS3200
Note
•
Natural convection must be possible above and below the device. A clearance of 200 mm
must be observed.
•
When two heating controllers are mounted one above the other, you must ensure that the
heat emitted from the lower device is routed past the upper device.
Remove surface protection
Remove the surface protection on the front and rear of the device before installation.
Содержание SIPLUS HCS3200
Страница 1: ......
Страница 2: ......
Страница 8: ...Introduction 1 1 Introduction SIPLUS HCS3200 8 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 12: ...Safety notes 2 2 IT security SIPLUS HCS3200 12 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 16: ...Description 3 4 System configuration SIPLUS HCS3200 16 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 24: ...Mounting 5 3 Final work SIPLUS HCS3200 24 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 44: ...Functions 8 6 Temperature monitoring SIPLUS HCS3200 44 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 66: ...Technical data 12 2 Dimension drawings SIPLUS HCS3200 66 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 74: ......