Configuration
8.3 Device/hardware configuration in the TIA Portal
SIPLUS HCS4200
68
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
8.3.3
Configuration parameters
8.3.3.1
CIM / POM configuration parameters
The configuration parameters are directly assigned to the respective modules and are set
during device configuration. They are transferred automatically on start-up and during re-
parameterization.
CIM parameters
Description
Range of values
Rated voltage for line voltage compensation
•
207 to 300 V
Parameters for POM low-end
Description
Value range
Control mode
(Set once per POM)
•
Half-wave control (default):
Phase LX1
(Set once per POM)
•
Connected (default)
•
Not connected
Phase LX3
(Set once per POM)
•
Connected (default)
•
Not connected
Response to errors
(Set per channel)
•
Channel substitute value 0 (default)
•
Channel value retained
Parameters for POM mid-range
Description
Value range
Control mode
(Set once per POM)
•
Half-wave control (default):
•
Soft start version 1
•
Soft start version 2
•
Soft start version 3
Phase LX1
(Set once per POM)
•
Connected (default)
•
Not connected
Phase LX3
(Set once per POM)
•
Connected (default)
•
Not connected
Response to errors
(Set per channel)
•
Channel substitute value 0 (default)
•
Channel value retained