background image

Operating Instructions SIPLUS CMS4000 IFN VIB-A 

 

 

 

 

 

 

 

Preface 

 

 

 

 

Product Overview 

SIPLUS

 

CMS4000 

 

 

 

Installation 

Interface Node 

 

 

 IFN VIB-ACC (IFN VIB-A)  

Wiring 

 

 

 

6AT8000-1BB00-4XA0 

Commissioning and Diagnosis 

 

 

 

 

Technical Data 

 

 

 

 

Appendix 

Operating Instructions - English 

 

 

Release 2014-11 

  

 

 
 
SIPLUS CMS4000 IFN VIB-A 
Operating Instructions, 11/2014, A5E02297871A-AA 

 

1

 

 

 

Siemens Parts

Содержание SIPLUS CMS4000 IFN VIB-A

Страница 1: ...US CMS4000 Installation 3 Interface Node IFN VIB ACC IFN VIB A Wiring 4 6AT8000 1BB00 4XA0 Commissioning and Diagnosis 5 Technical Data 6 Appendix 7 Operating Instructions English Release 2014 11 SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 1 Siemens Parts ...

Страница 2: ...rk on the equipment Qualified persons are defined as persons who are authorized to commission to earth and to tag circuits equipment and systems in accordance with established safety practices Intended Use Please note the following Warning This device and its components may only be used for the applications described in the catalog or technical description and only in connection with devices or co...

Страница 3: ...3 3 3 1 Installation 13 3 3 2 Disassembling 13 3 4 Label Plate 14 4 Wiring 15 4 1 General Rules and Regulations for operation of IFN VIB A 15 4 2 IFN VIB A 16 4 2 1 Connecting IFN VIB A to the ground SHIELD 16 4 2 2 Connecting M12 plugs 17 4 2 3 IEEE1394 Connection LNK 19 4 2 4 Power Supply Connection PWR 20 4 2 5 Messeingänge 21 4 2 6 Cable Traction Relief 23 4 2 7 Sealing of not used round conne...

Страница 4: ... 2 3 Measurement input CH1 CH6 31 6 2 4 Filter characteristic Channel CH1 CH6 34 6 2 5 Functional earth SHIELD 34 6 2 6 Environmental conditions 35 6 2 7 Construction assembly 35 6 2 8 Approval 36 6 3 Use of the CMS4000 in Zone 2 potentially explosive atmospheres 36 7 Appendix 37 7 1 Order Numbers 37 7 2 Dimensional Drawing 38 7 3 Service Support in the Internet 39 7 4 List of Abbreviations 39 SIP...

Страница 5: ...omponents 1 3 Validity of this Document This document is valid for the Interface Node IFN VIB A 1 4 Modification compared with the Previous Version None Notice You will find the version of the operating instructions in the number of the footer A5E02297871A AA 1 5 CE Marking The Interface Node IFN VIB A meets the requirements and objectives of the EG Guideline according to 2004 108 EG 1 6 Standards...

Страница 6: ...ng and diagnosis Chapter 5 Order Numbers Chapter 7 List of abbreviations with explanation of the general definitions of the used terms Chapter 7 1 9 Recycling and Disposal The IFN VIB A is environmental compatibility and recyclable For environmentally compatible recycling and disposal of your old device contact a certified waste disposal for electronic SIPLUS CMS4000 IFN VIB A Operating Instructio...

Страница 7: ...dustrial plants SIPLUS CMS is a modular scalable analysis and diagnosis system It is optimized for reaction less measurement of analog binary and numerical data SIPLUS CMS can be integrated in existing and new industrial plants SIPLUS CMS can be integrated into the TIA Architecture Picture 1 Typical configuration SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 7 Siemens Par...

Страница 8: ...bust construction and the degree of protection IP67 The compact design of the IFN VIB A enables the application in space saving ranges Easy handling of IFN VIB A provides a fast commissioning and maintenance The product is designed for the application on a DIN Rail or for mounting angles Display The IFN VIB A has one display LED IEPE Sensor connectors IEEE1394 connections and one connection for Po...

Страница 9: ...mp for DIN Rail mounting Operating Instructions compact Unpacking and Checking After unpacking please check the packet for completeness and all parts for transport damages Warning Do not use any parts that show signs of damage SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 9 Siemens Parts ...

Страница 10: ...ing angles Dimensions and Expansion Spaces Chart 1 Dimensions Dimensions mm with DIN rail with mounting angles Installation face length 86 86 Installation height 210 243 Installation depth 96 97 Picture 3 Correct Installation Position Caution The spaces which are specified in chapter 6 on top underneath and in front of the device have to be kept SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2...

Страница 11: ...s installed on the device Procedure Hang the upper table track of the device on the DIN rail and push it down towards the DIN rail so that it snaps in Picture 4 Installation of the device IFN VIB A on a DIN rail Caution During operation with vibration load use an attachment with mounting angels 1 2 3 SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 11 Siemens Parts ...

Страница 12: ...re Dissemble all electronic connection cables Remove the device from the DIN rail Push the device down against the DIN rail and hang it out Picture 5 Disassembly of the IFN VIB A from the DIN rail 1 3 2 SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 12 ...

Страница 13: ...in the equipment pack Order Number see chapter 7 1 Procedure Connect the mounting angles with the included screws and ring washers to the two con nection positions on the device backside top and bottom Install the device on a stable base Picture 6 Connection of the mounting angels on the device e g backside below 3 3 2 Disassembling Procedure Dissemble all electronic connection cables Demount the ...

Страница 14: ... plate The label plate is exchangeable Exchanging the label plate 1 Push the screwdriver in the small opening on the bottom edge of the label plate and hang it out Picture 7 Label Plate 2 Push the label plate with the finger in the indentation SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 14 ...

Страница 15: ...ernative Notice Controlled power adaptor SITOP SMART EMV Interference filter Company TIMONTA e g Type FMLB 0109 0640 SMD Ferrite on both power supply ledges Company WÜRTH ELEKTRONIK e g No 74271222 Protection against external electrical influences The following chart shows what you have to observe for the protection of electrical influ ences or faults Chart 4 Protection of electrical influences At...

Страница 16: ...ented with cable cross section of 2 5mm 2 1 Isolate the grounding cable and squeeze a cable lug at the end of the line M4 ring eye 2 Screw the cable lug to the device as shown in the picture The recommended torque is 3 Nm Picture 8 Connecting IFN VIB A to the ground SHIELD SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 16 ...

Страница 17: ...he M12 connector in vertical position in the socket plug so that the slot from the connector and knurled ring nut are superposed Picture 9 Connecting M12 connector 2 Twist the M12 socket plug with the knurled ring nut tight until it snaps about 1 2 rota tion Picture 10 M12 socket plug interlocking Knurled ring nut SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 17 Siemens P...

Страница 18: ...et plug connection Caution Avoid canting between M12 connector and socket plug Only when the installation is correct the protection category IP67 and safe contacting is guaranteed Never pull and insert cables and plugs when the ambient temperature is 0 Celsius and below SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 18 ...

Страница 19: ...A Twisted pair B 5 Masse 6 TPB Twisted pair B 7 TPB Twisted pair A 8 Power supply only relevant when coupling with MCN11 Caution In configurations with ION devices ION PROFIBUS DP Spy T001 ION BINARYINPUT T001 RPN IEEE1394B and IFN devices IFN VIB A IFN AI in a common communication line choose for the first device after the controller PC an ION Fiber Optical Cable Coupling The product SIPLUS CMS40...

Страница 20: ...ow voltages SELV complying with IEC950 EN60950 VDE0805 can be connected to the power supply terminals The power supply unit for the supply of the IFN VIB A has to meet NEC Class 2 range of voltage 18 32 V Never operate the IFN VIB A with AC voltage or DC voltage higher than 32 VDC Connection Assignment Chart 6 Connection assignment PWR PIN Assignment Wire color Display 1 M24 earth brown 2 24V DC 1...

Страница 21: ...5 Input IEPE Sensor 5 CH6 Input IEPE Sensor 6 or analog input signal Caution SIPLUS CMS4000 X Tools controls the switching of CH6 between IEPE Sensor or analog input signal Use the tool for parameterization Connector assignment analog input CH1 CH6 Chart 8 Connector assignment IEPE sensor input CH1 CH6 PIN Assignment Wire color Display 1 M earth brown 2 free white 3 Signal blue 4 free black 5 free...

Страница 22: ...ang PIN Assignment Wire color Display 1 M earth brown 2 24 V signal white 3 free blue 4 free black 5 free grey or green yellow Shielding measurement CH1 CH6 Caution Use only shielded lines where the shielding is applied to one side of the IFN VIB A plug housing SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 22 ...

Страница 23: ...on relief 4 2 7 Sealing of not used round connectors Seal all not used round connectors with M12 end caps in order to reach the degree of protection IP 67 Observe the correct fitting of the end caps Order Number Coping Set see chapter 7 1 SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 23 Siemens Parts ...

Страница 24: ... VIB A mounted view chapter 3 2 IFN VIB A wired view chapter 4 5 1 3 Commissioning of IFN VIB A Picture 12 Start up IFN VIB A Power On Power LED flashing Startup ready LNK LED on Verify IEEE1394 bus and X Tools device driver LNK LED flashing Diagnosis via X Tools Start of transmitting data CH LED off CH LED no no no no yes yes yes on flashing yes Connection between PC and X Tools is established No...

Страница 25: ...scription power Indicator Color green Condition off no operation voltage blinks firmware operates Name ERR Description error Indicator Color red Condition off no error on error Name LNK Description indicator for connection to the controller Color yellow Condition off no connection to the controller on connection to the controller established blinks data exchange with the controller Name CH1 6 Desc...

Страница 26: ... Spy ION BI ION AI ION VIB A in a single bus line with a MICROBOX PC take account of Connect the ION and IFN in a single line at plug 2 Port 3 The order of the nodes is not relevant If an existing MICROBOX PC with CMB IEEE1394A T011 is used please verify that plug 2 is connected with Port 3 of the PC 104 card A mixed configuration at plug 1 PC 104 card Port 2 or Port 1 could cause communica tion p...

Страница 27: ...Operating Instructions SIPLUS CMS4000 IFN VIB A Picture 14 MICROBOX PC with CMB IEEE1394A PC 104 card SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 27 Siemens Parts ...

Страница 28: ...N 61000 4 3 2008 EN 61000 4 3 2006 A1 2008 DIN EN 61000 4 4 2005 EN 61000 4 4 2004 DIN EN 61000 4 5 2007 EN 61000 4 5 2006 DIN EN 61000 4 6 2008 EN 61000 4 6 2007 Installation Guide Lines The product meets the requirements if you meet the installation instructions and safety related notices as described in this commissioning manual Conformity Certificates The EC Declaration of Conformity is availa...

Страница 29: ...Safety information Warning Personal injury and damage to property may occur In hazardous areas injury to persons and material damage may occur if you disconnect plug in connections during operation of a CMS4000 system Always switch off the power to the CMS4000 system when disconnecting plug in connec tions in potentially explosive atmospheres Warning Explosion hazard If you replace components comp...

Страница 30: ...n 3 only allowed for appropriate IEPE sensors Power supply Parameter min typ max Unit Connector one connector male 5 pin M12 Supply voltage DC 19 2 24 32 V only under certain conditions 3 18 32 V Over voltage protection DC permitted for max 500ms 2 35 V Supply current DC Us 18V DC 240 mA Us 24V DC 200 mA Us 32V DC 150 mA Reverse voltage protection Us 0 32V DC yes Reverse current Is 32V DC 5 uA Is ...

Страница 31: ... damping at 40 kHz see filter characteristic Measurement input Parameter min typ Max Unit Input voltage DC Rated voltage 0 75 0 75 V Quiescent point DC of the sensors 8 12 V Constant DC current feed 4 5 2 7 mA DC Input resistance 330 kΩ Input frequency 0 0001 20 6 kHz Coupling inputs AC Cross talk attenuation CTA Channel to channel f 1kHz 69 dB Signal to noise ratio SNR 57 dB Sampling rate each ch...

Страница 32: ... point DC of the sensors 8 12 V Constant DC current feed 4 5 2 7 mA DC Input resistance 330 kΩ Input frequency 0 005 20 6 kHz Coupling inputs AC Cross talk attenuation CTA Channel to channel f 1kHz 73 dB Signal to noise ratio SNR 70 dB Sampling rate each channel 192 kSPS Down sampling rate to parameterize with X Tools 4 8 16 24 32 48 96 kSPS 4 96 kSPS Accuracy 100 Hz till 1 kHz Abs based on full s...

Страница 33: ...unit Input voltage DC Rated voltage 30 V Input resistance 50 kΩ Input frequency 0 DC 1 kHz Coupling inputs DC Cross talk attenuation CTA Channel to channel f 1kHz 78 dB Signal to noise ratio SNR 69 dB Sampling rate each channel 192 kSPS Down sampling rate to parameterize with X Tools 4 8 16 24 32 48 96 kSPS 4 96 kSPS Accuracy Abs based on full scale 1 Temperature dependency 125 83 ppm K Galvanic i...

Страница 34: ... 00 40 00 30 00 20 00 10 00 0 00 10 00 1 E 03 1 E 04 1 E 05 1 E 06 f Hz a dB Anti aliasing 8 Ordnung 6 2 5 Functional earth SHIELD Chart 15 Functional earth SHIELD Functional earth SHIELD Parameter min typ max Unit Connection Screw with detent clip M4 Cable recommended cross section 2 5 mm 2 Shield resistance Main electronic to SHIELD 1000 kΩ Shield capacitance Main electronic to SHIELD 30 nF SIPL...

Страница 35: ... IP67 Height of construction over zero 2000 m 6 2 7 Construction assembly Chart 17 Construction assembly Construction assembly Case Aluminium Dimensions with plug H x W x D in mm 210 x 86 x 87 without mounting 210 x 86 x 96 DIN rail mounting 243 x 86 x 97 mounting angle Mounting Standard DIN rail DIN EN 60715TH35 15 Optional Mounting angle Order Number in chapter 7 1 Minimum distances front top bo...

Страница 36: ...ECEx approval IECEx DEK 14 0040 X EAC certification KC certification RCM certification 6 3 Use of the CMS4000 in Zone 2 potentially explosive atmospheres See product information Deployment of the modules in zone 2 potentially explosive atmospheres http support automation siemens com WW view en 104933030 SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 36 ...

Страница 37: ...B50 1AA2 6AT8000 2AB50 1AB0 6AT8000 2AB50 1AC0 6AT8000 2AB50 1AE5 IEEE1394 IFN PC cable Length 40 cm Length 200 cm Length 450 cm 6AT8000 2AB20 1AB0 6AT8000 2AB20 1AC0 6AT8000 2AB20 1AE5 IEEE1394 IFN MCN cable Length 30 cm 6AT8000 2AB20 2AA2 Sensor signal cable Length 200 cm Length 500 cm Length 1000 cm 6AT8000 2AB40 1AA2 6AT8000 2AB40 1AA5 6AT8000 2AB40 1AB0 24 V Power cable Length 200 cm Length 5...

Страница 38: ...Operating Instructions SIPLUS CMS4000 IFN VIB A 7 2 Dimensional Drawing SIPLUS CMS4000 IFN VIB A Operating Instructions 11 2014 A5E02297871A AA 38 ...

Страница 39: ...pport The bulletin board a worldwide knowledge exchange for users and experts Your local representative for Industry Automation Drives Technologies via our representatives database Information about on site services repairs spare parts and lots more you will find under Support 7 4 List of Abbreviations Abbreviation Item CH Channel CMS Condition Monitoring System IEEE Institute of Electrical and El...

Отзывы: