Siemens SiPass integrated Скачать руководство пользователя страница 35

 

 

Host event tasks 

Targets / Commands 

A6V11144326 

 

35 | 66 

 

7.2

 

Targets / Commands 

 

Target 

Command 

Description 

ACC Trigger 

Set Trigger 

An ACC Trigger allows you to trigger a Controller 

event task from a software event, like a Host 

event task. 
This Command activates the trigger selected. 

Any Controller Event tasks of type “Host Control” 

will be listed in the Location drop-down menu. 

Clear Trigger 

This Command clears the trigger selected, if it is 

currently activated. 

Access Point 

Allow Access 

Allow access as if a valid card has been 

presented at the reader. The door lock will re-

lock after the defined Latch time. 

Lock Door 

Locks the door temporarily until the next change 

in Time Schedule. 

Unlock Door 

Unlocks the door temporarily until the next 

change in Time Schedule. 

Set Mode “Card Only”

  Enables Card Only operation at an access point. 

Refer to Operational modes page 22 for more 

information. 

Set Mode “Card and 

PIN”

 

Enables Card and PIN operation at an access 

point. Refer to Operational modes page 22 for 

more information. 

Set Mode “H. V. Card 

Only”

 

Enables Host Verification Card Only operation at 

an access point. Refer to Operational modes 

page 22 for more information. 

Set Mode “H. V. Card 

and PIN”

 

Enables Host Verification Card and PIN 

operation at an access point. Refer to 

Operational modes page 22 for more 

information. 

Set Mode “V. O. Card 

Only”

 

Enables View Only Card Only operation at an 

access point. Refer to Operational modes page 

22 for more information. 

Set Mode “V. O. Card 

and PIN”

 

Enables View Only Card and PIN operation at an 

access point. Refer to Operational modes page 

22 for more information. 

Set Mode “D. R. Card 

Only”

 

Enables Delayed Reporting Card Only operation 

at an access point. Refer to Operational modes 

page 22 for more information. 

Set Mode “D. R. Card 

and PIN”

 

Enables Delayed Reporting Card and PIN 

operation at an access point. Refer to 

Operational modes page 22 for more 

information. 

Set Mode “Disabled”

  Disables an access point. Refer to Operational 

modes page 22 for more information. 

Restore Access Mode  Restores the previous access mode at an access 

point. Refer to Operational modes page 22 for 

more information. 

Reset Reader Tamper  Resets the reader tamper. Only applies to the 

Siemens reader range. 

Block Door 

Blocks the door and prevents cards from being 

used to gain access at the door using the 

selected reader. 

Содержание SiPass integrated

Страница 1: ...Access Control SiPass integrated Reference Guide MP 2 80 A6V11144326 Smart Infrastructure 07 09 2020 ...

Страница 2: ...tance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Edition 07 09 2020 Document ID A6V11144326 Siemens Switzerland Ltd 2020 ...

Страница 3: ...Image Formats 6 3 System Functions 7 4 Alarm Class 12 5 Operational Modes 19 6 Manual Override 24 7 Host event tasks 28 7 1 Sources 28 7 2 Targets Commands 35 8 Controller Event Tasks 41 8 1 Sources 41 8 2 Commands 49 9 ASP Trigger States 54 10 ASP Effect States 62 ...

Страница 4: ......

Страница 5: ...n SiPass integrated is the leading access control software on the market This User s Reference Manual provides a number of reference data tables that may assist you when assigning system functions defining alarm classes assigning operational modes to points performing manual commands creating event tasks and sending system messages ...

Страница 6: ...ap BMP 16 7 million CALS Computer aided Acquisition and Logistics Support CAL 2 DCX DCX 16 7 million EPS EPS 16 7 million GEM IMG IMG 16 GIF GIF 256 Halo CUT CUT 256 ICO ICON ICO 16 IFF Amiga IFF 16 7 million IOCA ICA 2 JPEG JPG 16 7 million LaserView LV 2 MacPaint MAC 2 Microsoft Windows Paint MSP MSP 2 PCX PCX 16 7 million PSD Photoshop PSD 16 7 million Photo CD PCD 16 7 million PICT PCT 16 7 mi...

Страница 7: ... is prevented from creating or deleting such records v view The operator is granted access to retrieve and view records relating to specific system functions but is prevented from creating deleting or modifying such records The following table lists the system functions that may be assigned to an operator group together with a brief description of each function The table also lists the privilege l...

Страница 8: ...an configure CCTV components via the SiPass interface none c e v CCTV Operation Determines whether the operator can operate CCTV components via the SiPass interface none c e v Components Provides privileges for the Components dialog The level applied to the Components system function will take prece dence over other system functions for example Points none c e v Credential Profile Provides privile...

Страница 9: ...d full synchronization of cardholder databases across the GCM system none c Graphics Provides privileges for the Graphics Module including site plans drawings symbols and card templates none c e v Guard Tour Configuration Provides privileges for the configuration of Guards Tours and Tour Groups none c e v Guard Tour Operation Provides privileges for the starting stopping and monitoring of guard to...

Страница 10: ...ewing the Overview window which displays a summary of system components none c e v PIN Assignment Provides privileges for creating modifying deleting or viewing PIN numbers assigned in the Cardholder dialog none c e v Point Provides privileges for creating modifying deleting and viewing output input and access points none c e v Point Group Provides privileges for creating modifying and deleting po...

Страница 11: ... dialog none c e v Time and Attendance Provides privileges for creating viewing modifying and deleting details of the Time and Attendance Interface none c e v Time Schedule Provides privileges for creating modifying and deleting Time Schedules none c e v Virtual Monitor Provides privileges for viewing live videos for IP and DVR cameras none v Visitor Provides privileges for creating viewing modify...

Страница 12: ...d Card activates APB area either ON A card was used to secure an area Card activates APB area either OFF A card was used to unsecure an area Card activates floor A card was used at a card reader to secure a floor Card did not activate a floor A card was used unsuccessfully at a card reader to secure a floor Door Time Schedule Active A door has reverted to normal Time Schedule control after being m...

Страница 13: ...cility Code on a card was read at an access point Each site has a site specific Facility Code Card number limit The maximum number of cards supported by the hardware processor has been reached An invalid PIN number An invalid PIN Personal Identification Number was entered at an access point Bad daily code An invalid Daily Code was entered at a keypad that requires a Daily Code to be entered Indepe...

Страница 14: ...hedule Violation A card was read at a reader outside the normal scheduled time for that card Elevator Offline Denied The HLI Elevator is offline Elevator Override Denied The HLI Elevator is in external override Elevator Access Collision The HLI Elevator is in access collision because another access session is in progress Intrusion Control Disabled Intrusion Control has been disabled at the reader ...

Страница 15: ...ovement in the area and has raised a normal alarm Video Loss The communication link between the camera switcher and the monitor has been lost Motion Alarm The camera has detected movement and has raised an alarm Device Communication Back The device has re established communication with the server Communication Lost The device has lost communication with the server Door Interlocking Interlocking Op...

Страница 16: ...e on the device has been enabled physically Input tamper or fault cleared The input tamper state has been cleared fixed Sintony Input Sealed The Sintony input is inactive and the input area could be armed Sintony Input Isolated Overrides the Sintony Input Unsealed therefore allows the area to be armed and also disables the processing of this input in the intrusion system Alarm The input is in alar...

Страница 17: ...on this area are still unarmed Intrusion Area Part Armed The intrusion area has been part armed Intrusion Area Part Armed B The SPC intrusion area has been part armed B SPC only Intrusion Area Disarmed The intrusion area has been disarmed Alarm An armed intrusion area has been violated Arming Failed An attempt to arm an intrusion area has failed OPC Point Normal The OPC Point is in a normal state ...

Страница 18: ...e server has been lost Unit Tamper active The tamper input on a unit is active Memory Full The memory of the unit has reached maximum capacity Power Lost Power has been lost from the unit Memory Overflow The backup flash memory is full SALTO System Online SiPass integrated is connected to the SALTO System SALTO System Offline SiPass integrated is not connected to the SALTO System ...

Страница 19: ...access point to gain valid access also a snapshot of the cardholder is taken as they enter and stored in the database Double Single Arming A card must be presented at the access point by a valid cardholder A double card badge will arm the area and a single card badge will disarm operation for all assigned intrusion areas Card Only Delayed Reporting This mode is used for access points for entry or ...

Страница 20: ... at the access point as well as a PIN must be entered in order to arm or disarm the intrusion area Press 1 and then select E to arm the area or press 0 and then E to disarm Programmable Authorization Card Only A card must be presented at the access point for an authorization started event to be generated Access is only granted if an authorization granted event is received Programmable Authorizatio...

Страница 21: ... is entered and the users just present their card previous pressing of the E or key for arming selection has no effect on this However if the card is badged first after selecting an arming action the E or key must be pressed after entering the PIN For devices that do not require a button to be pressed after entering the PIN Some devices like DC12 DC22 DC800 GrantaCotagCard and GrantaSwipeCard do n...

Страница 22: ... If the door is not returned to a normal state within the Pre Alarm time period the Door Held Alarm will sound and will be registered in the alarm queue The Door Held Alarm will auto matically stop when the door returns to a normal state Door Frame Dual Timer Defines the input point as a door contact sensor that monitors the open or closed state of the door The input point will use both the Pre Al...

Страница 23: ...al except if the cardholder has isolation privileges they can override a point if the point is not sealed Intrusion Area No Seal Check The input seals are not checked when intrusion area is armed Defines the input type as normal Intrusion Area Instantaneous Defines the input type as normal except that when the area is secured there are no entry or exit delay times Intrusion Area Hand Over Allows s...

Страница 24: ... Lock Door The door latch will be locked until the next unlock command is received The Duration can be set to Until time schedule change Permanents Reader Buzzer Off The Reader buzzer is turned off Only applies to the Siemens reader range Reader Buzzer On Reader buzzer is turned on Only applies to the Siemens reader range Reset Reader Tamper Resets the reader tamper input Only applies to the Sieme...

Страница 25: ...nt to Standard Dual Custody Mode Set mode Supervisory Dual Custody Set the access point to Supervisory Dual Custody Mode Set Mode V O Card and PIN Sets the point s operation mode to View Only Card and PIN Set Mode V O Card Only Sets the point s operation mode to View Only Card Only Unblock Door Turns off the block door command Returns the door to its normal programmed mode of operation Unlock Door...

Страница 26: ...orarily if the output is currently unlocked The Duration can be set to Until Time Schedule Change Permanent Duration time can be specified in the HH MM SS format Single Pulse The output will activate a single pulse Slow Pulse The output will activate in slow pulse mode Toggle Point The state of the output will be toggled to the reverse state Unsecure Unlock Unlocks the output temporarily if the ou...

Страница 27: ...he all SPC zones in alarm on the panel Elevator Cancel Permanent Action Any current Permanent Command Event Task or Access Internal Action operating on the point will be cancelled The next Control State in the Control State Queue will take effect Floor off security unsecure Takes the floor off security until the next change in Time Sched ule Floor on security secure Places the floor on security un...

Страница 28: ...ly Code Standard Dual Custody mode set Access Point mode set to Daily Code Supervisory Dual Custody mode set Access Point mode set to Daily Code Access denied Hard Perimeter Violation A cardholder has been denied entry due to hard Anti Passback area restrictions Access Denied Intrusion Area Armed A host event task is triggered when a card is presented at a reader is denied entry because the area t...

Страница 29: ...ction the alarm associated with the access point and the alarm time out Operator Normal A host event task is triggered when the nominated access point changes to a normal state Operator Restore A host event task is triggered when the nominated access point attains Restored status Operator Waiting for Normal A host event task is triggered when a restorable alarm at the nominated point has been ac t...

Страница 30: ...vent task is triggered when a card that is void is swiped at a card reader Access Point Group Same as Access Points with less States options See above Anti Passback Area Point Area Count Reset An Area count has been reset Area Mode Changed An Area mode has been changed Capacity Empty The area is vacant Capacity Exceeded An event task is triggered when the count for the number of cardholders curren...

Страница 31: ...from the camera is restored Camera Point Group Alarm A host event task is triggered when a camera point group enters the alarm state Normal A host event task is triggered when a camera point group returns to the normal state Database Database Synchronization failed A host based event task is triggered when the database synchronization process has failed Database Synchronization OK A host based eve...

Страница 32: ...vent task is triggered when the nominated input point group enters a Tamper state Normal An event task is triggered when the nominated input point goes into the normal state Operator Alarm An event task is triggered when the nominated input point goes into alarm Operator Alarm Actioned An event task is triggered when an alarm associated with the nominated input point is actioned by an operator Ope...

Страница 33: ...riggered when the nominated output point is locked Note Locked Temp does not trigger an event task Operator Alarm An event task is triggered when the nominated output point goes into alarm Operator Alarm Actioned An event task is triggered when an alarm associated with the nominated output point is actioned by an operator Operator Alarm Not Actioned An event task is triggered when the operator fai...

Страница 34: ...se cannot be detected Operator Alarm An event task is triggered when the nominated controller enters an alarm state Operator Alarm Actioned An event task is triggered when an alarm associated with the nominated controller is actioned by an operator Operator Alarm Not Actioned An event task is triggered when the operator fails to action an alarm associated with the nominated controller before the r...

Страница 35: ...ation Card Only operation at an access point Refer to Operational modes page 22 for more information Set Mode H V Card and PIN Enables Host Verification Card and PIN operation at an access point Refer to Operational modes page 22 for more information Set Mode V O Card Only Enables View Only Card Only operation at an access point Refer to Operational modes page 22 for more information Set Mode V O ...

Страница 36: ... operation mode defined in the Components screen Unlock Door Override Door Interlocking Unlocks the door and ignores any Door Interlocking configuration Allow Access Override Door Interlocking Allows access and ignores any Door Interlocking configuration Intrusion Control Enable Enable Intrusion Control on the selected access point Intrusion Control Disable Disable Intrusion Control on the selecte...

Страница 37: ... a pre configured alarm on the specified monitor Refer to the CCTV User s Guide for more information Database Database Backup Data Performs a backup of the SiPass integrated data files Database Backup Binaries Performs a backup of the SiPass integrated binary files Database backup Historical Performs a backup of the historical data Database Backup Runtime Performs a backup of the runtime data Data...

Страница 38: ...n Area Arms inputs which are marked as Part Arm B SPC only Intrusion Area Point Group Same as Intrusion Area Points See above Message Forwarding Forward to Pager s Allows a message to be forwarded to one or more pagers if the host event task has been triggered Send to all OPC Clients Sends details of the trigger to all OPC connections defined in the Components dialog Forward to Email s Allows a me...

Страница 39: ...nores any Door Interlocking configuration Allow Access Override Door Interlocking Allows access and ignores any Door Interlocking configuration Output Point Group Same as Output Points See above Reporting Print Print the selected report SaveAs Exports the selected report to a file Email Forwarding Export the selected report to a file and then email it to selected cardholders System Turn Printer Of...

Страница 40: ...nitialization for the selected unit Compact Database Performs compacted database backup database for the selected unit This operation maybe required when unit s Backup Flash memory becomes full Establish Dial up Connection Initiates a dialup connection with the SiPass integrated Server The audit trail in the unit will be automatically uploaded upon a successful connection Workgroup Void Voids the ...

Страница 41: ...t to Daily Code No Additional Access mode set Access Point mode set to No Additional Access No Dual Custody mode set Access Point mode set to No Dual Custody mode PIN as Card mode set Access Point mode set to Daily Code Standard Dual Custody mode set Access Point mode set to Daily Code Supervisory Dual Custody mode set Access Point mode set to Daily Code Disable Intrusion Control Intrusion Control...

Страница 42: ...ity Full An event task is triggered when the number of cardholders currently in the anti passback area has reached the programmed capacity Capacity Not Empty The area is no longer empty Capacity Not Full The number of cardholders in the area does not exceed the defined maximum Four Eyes Access Alarm An event task is triggered when an area under four eyes control has been violated Four Eyes Access ...

Страница 43: ... does not match the Print Revision Number stored in the database has been badged at an access point The Print Revision Number is updated each time the card is printed This applies only to Siemens proprietary 52 bit card format Door Interlocking In Progress Collision An event task is triggered if a card is badged a second time at any door in a Door Interlocking set while the first door interlocking...

Страница 44: ...sabled An event task has been triggered when a card has been voided after the cardholder has made three consecutive incorrect PIN entries in the facility Point Disabled An event task has been triggered when an access point has been disabled Soft Anti Passback error An event task has been triggered when a soft Anti Passback error has occurred Soft Perimeter Violation An event task has been triggere...

Страница 45: ...ations OK An event task has been triggered when the communications between the SiPass integrated Server and a controller has been restored Tamper Active An event task has been triggered when the tamper input to the ACC registers an alarm Tamper Normal An event task has been triggered when the tamper input to the ACC registers returns to a normal state Unit Reset An event task has been triggered wh...

Страница 46: ...k is triggered when the selected bank floor is unsecured Host Control Cleared This Type allows a Controller Event Task to be triggered from a Host Event Task An event task is triggered when the Controller Event Task has not been triggered or has been reset Set An event task is triggered when the Controller Event Task has been triggered Input Point Device Active An event task is triggered when the ...

Страница 47: ...ut Tamper An event task is triggered when a device has registered that a supervised input point has been tampered with Input tamper or fault cleared The input tamper state has been cleared fixed Input Unsealed Input has failed a seal check when arming an Intrusion Area Pass back Tamper An event task is triggered when a device has registered that a supervised request to exit input has been tampered...

Страница 48: ...essed at an access point with a keypad Output Point Locked Output point has been locked Unlocked Output point has been unlocked Reader Smart Card Event An event task is triggered when an event task is triggered when a MIFARE smart card has been badged at an access point Standard Card Event An event task is triggered when a standard access card non smart card has been badged at an access point Time...

Страница 49: ...point Refer to Operational modes page 22 for more information Set Mode H V Card Only Enables Host Verification Card Only operation at an access point Refer to Operational modes page 22 for more information Set Mode H V Card and PIN Enables Host Verification Card and PIN operation at an access point Refer to Operational modes page 22 for more information Set Mode V O Card Only Enables View Only Car...

Страница 50: ...t to Standard Dual Custody Mode Set mode Supervisory Dual Custody Set the access point to Supervisory Dual Custody Mode Restore Dual Custody Config Mode Restores Dual Custody to the configured mode Report Dual Custody Config Mode Reports the configured Dual Custody mode Set No Additional Access Set the additional access for the selected access point to No Additional Access Set Daily Code additiona...

Страница 51: ... Interlocking Restore Door Interlocking Floor Bank Floor Secure Secures the specified elevator floor for all elevators within the same bank Bank Floor Unsecure Unsecures the specified elevator floor for all elevators within the same bank Bank Floor Enable Enables the specified elevator floor for all elevators within the same bank Bank Floor Disable Disables the specified elevator floor for all ele...

Страница 52: ...me for which you want the door to be unlocked into the Duration field using the format HH MM SS Lock Secures the selected output point Enter the time for which you want the door to be locked into the Duration field using the format HH MM SS Toggle Reverses the current status of the output point Slow Pulse Causes the output point to emit a slow pulse behaviour depending on the point type For exampl...

Страница 53: ...he next Control State in the Control State Queue will take effect Unlock Override Door Interlocking Unlocks the output and ignores any Door Interlocking configuration Allow Access Override Door Interlocking Allows access and ignores any Door Interlocking configuration Run Host Task N A Select a pre defined host event task from the Target drop down list The host event task will be executed when the...

Страница 54: ...bled Door Opened Logical state of Doorframe input Input Enabled True False Enabled state of input Tamper Logical State Input Tamper Input Fault Tamer or Fault Cleared Indicates Tamper or Fault state Intrusion State Input Alarm Input Normal Input Tamper Input Disables Input Isolated Input Logical state related to intrusion Zone inputs Physical Enable State Input Disabled HW Input Enabled HW Indicat...

Страница 55: ...ed in hardware Unsealed Sintony input state Output Point Event Conditio n Dual State Open Closed Output state Open Closed only Aux Output State Open Closed Slow Pulse Fast Pulse Auxiliary Output state Access Point Event Conditio n Reader Online State Online Offline Communication status of the reader Reader Tamper State Tamper Tamper Okay Tamper state of the reader Dual custody state Dual Custody C...

Страница 56: ...Access Daily Code Pin as Card The additional access mode of the reader Dual Custody Mode No Dual Custody Standard Dual Custody Supervisory Dual Custody The dual custody access mode of the reader Intrusion Control Mode False True The Intrusion Control Mode of the reader Green LED State LED On LED Off Blink LED The Green LED state of the reader Red LED State LED On LED Off Blink LED The Red LED stat...

Страница 57: ... of the APB Area User Count Integer Value Indicates the number of users that are currently in the APB Area Event Only Area Reset Event True All Users in the APB Area have been cleared Anti Passback Area Workgrou p Event Conditio n Empty State False True Indicates whether the APB Area is empty for the given workgroup Capacity State Capacity Full Capacity Exceeded Capacity Okay Indicates whether the...

Страница 58: ... Bank Floor Event Only Floor Selected True Bank Floor Selected Event Conditio n Enabled State False True Indicates if Bank Floor is Enabled Disabled for Access Secure State False True Indicates Secured Unsecured state of Bank Floor Door Interlock Event Conditio n Enabled False True Indicates the state of door interlock State Operational Disabled Alarm Door Interlocking State of Interlocking Set In...

Страница 59: ...able Authorization status Unit Event Conditio n Comms ok False True Indicates the unit communication Event Conditio n Database Usage 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Indicates the percentage of Database Memory that has been used The memory is reported in 5 percentile bands Event Conditio n Runtime Memory Usage 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1...

Страница 60: ...on Host Access Denied Elevator Offline Elevator Override Elevator Access Colli sion Invalid Dual Custody Workgroup Limit Error Door Interlocking Access Collision Programmable Authorization Timeout Programmable Authorization Access Denied Card Events for Access Denied Other Access Event No Entry User Duress Card Ignored card Presented Accessibility card Presented Host Verification Card Low Battery ...

Страница 61: ...ly Booking Offset Type After End After Start Before End Before Start After setting up a venue an ASP activity can be configured to trigger an action before or after every booking start or stop Note The time for the action to take place before or after the start and stop of the venue booking can be set in minutes ...

Страница 62: ...t Point Stateless Effect Toggle Output True Toggles the door latch local elevator state of the output Alternative Effect Dual State Open Closed Output State of Door Latch Local Elevator Open and Closed only Regular Effect Unlock Override Interlock True Overrides the door interlock state setting the state of the Latch output to Unlock Stateless Effect Door Latch Allow Access Override Interlock Over...

Страница 63: ...ess Mode No Additional Access Daily Code Pin as Card The additional access mode of the reader Dual Custody Mode No Dual Custody Standard Dual Custody Supervisory Dual Custody The dual custody access mode of the reader Intrusion Control Mode False True The Intrusion Control Mode of the reader Alternative Effect Green LED State LED On LED Off Blink LED The green state of the reader Red LED State LED...

Страница 64: ...ccess Perform Door Interlock Exclusion command on door Programmable Authorization Granted False True Invoke Grant or Deny External Authorization command Anti Passback Area Regular Effect Reset Area True Command to clear all users from the APB Area Anti Passback Mode Hard Anti Passback Soft Anti Passback No Anti Passback Indicates the APB Mode of the APB Area Intrusion Zone Regular Effect Force Arm...

Страница 65: ...to configured Enabled state Disable True Disable Door Interlocking Set Counter Regular Effect Counter Value Integer Value Sets register containing the current counter value Preset Integer Value Sets the preset value of the counter Stateless Effect Increment Integer Value Increments the counter by the specified amount Decrement Integer Value Decrements the counter by the specified amount Timer Regu...

Страница 66: ...erland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice ...

Отзывы: