SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
135
Parameter assignment/Addressing
10
10.1
Overview of the parameters
10.1.1
Overview of parameters 1 to 5
Introduction
Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to
adjust the positioner to the actuator. Normally the parameter setup is sufficient to be able to
operate the positioner on an actuator.
If you want to get to know the positioner in detail, gradually try out the effects of the
remaining parameters by systematic testing
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter
Function
Parameter values
Unit
Type of position actuator
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator without sine correction)
ncSt (part-turn actuator with NCS)
-ncSt (part-turn actuator with NCS, inverse
direction of action)
ncSL (linear actuator with NCS)
1.YFCT
ncSLL (linear actuator with NCS and lever)
Nominal angle of rotation of the feedback message
1)
33°
2.YAGL
90°
Degrees
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......