Note
The fast digital inputs/outputs must be shielded.
7.10.3
Connecting digital inputs/outputs
Cable specification
Table 7-21
Cable specification at X122 / X132 / X142
Features
Version
Connector type
14-pin spring-loaded terminals
Number of cables that can be connected 1
Connection option
0.2 to 1.5 mm
2
Max. current carrying capacity
6 A
Max. cable length
30 m
Table 7-22
Connectable conductor cross-sections
Connectable conduc‐
tor cross-sections
Rigid
Flexible
Flexible, with end sleeve without plastic sleeve
Flexible, with end sleeve with plastic sleeve
AWG / kcmil
0.2 to 1.5 mm
2
0.2 to 1.5 mm
2
0.25 to 1.5 mm
2
0.25 to 0.75 mm
2
24 to 16
Stripped length
10 mm
Tool
Screwdriver
0.4 x 2.0 mm
Note
To achieve optimum interference suppression, shielded cables must be used to connect
measuring inputs or BEROs.
The following cable lugs may be used:
● Crimped cable lug to DIN 46234
● Pressed cable lug to DIN 46235
● Tube-type cable lug to SN 71322
● Tube-type cable lug "Klauke R Series", UL Category ZMVV
Connecting
7.10 Digital inputs/outputs
NCU 1760
80
Equipment Manual, 02/2020, A5E45627861B AB
Содержание SINUMERIK ONE NCU 1760
Страница 8: ...Table of contents NCU 1760 8 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 36: ...Description 3 5 Dual fan module NCU 1760 36 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 44: ...Dimension drawings 5 1 NCU 1760 dimension drawing NCU 1760 44 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 48: ...Installation 6 4 Mounting the NCU without spacers NCU 1760 48 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 150: ...Connectable components 11 3 PP 72 48D PN 2 2A PN NCU 1760 150 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 154: ...Spare parts accessories 12 2 SD card NCU 1760 154 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 156: ...Safety symbols NCU 1760 156 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 160: ...Appendix A 2 Documentation overview SINUMERIK ONE NCU 1760 160 Equipment Manual 02 2020 A5E45627861B AB ...