4.1.2
RI suppression measures
In addition to the protective grounding of system components, special precautions must be
taken to ensure safe, fault-free operation of the system. These measures include shielded
signal lines, special equipotential bonding connections, and isolation and shielding
measures.
Shielded signal cables
● For safe and smooth operation of the system, the specified cables must be used. Please
refer to the chapter titled Connection.
● For digital signal transmission, the shield must have a conductive connection at both sides
of the housing.
Cable definitions
● Signal cables (example)
– Data cables (Ethernet, PROFIBUS, PROFINET, sensor cables, etc.)
– Digital inputs/outputs
– Emergency Stop cables
● Power cables (example)
– Supply voltage 1 x 230 VAC or 3 x 400 VAC
– Motor cables
Rules for routing cables
In order to maximize noise immunity for the complete system (control, power unit, machine) the
following EMC measures must be observed:
● A minimum distance of 200 mm is to be observed between the signal lines and power cables.
● If necessary, signal and load cables may cross one another (if possible, at an angle of 90°),
but must never be laid close or parallel to one another.
● Only use cables approved by Siemens for the signal lines from and to the NCU.
● Signal cables may not be routed close to strong external magnetic fields (e.g. motors and
transformers).
● If signal lines cannot be routed a sufficient distance away from other cables, they must be
installed in grounded cable ducts (metal).
Additional information
You can find further information on interference suppression measures and the connection of
shielded cables here:
● Configuration Manual, EMC Guidelines
Application planning
4.1 Supplementary electrical conditions
NCU 1760
38
Equipment Manual, 02/2020, A5E45627861B AB
Содержание SINUMERIK ONE NCU 1760
Страница 8: ...Table of contents NCU 1760 8 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 36: ...Description 3 5 Dual fan module NCU 1760 36 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 44: ...Dimension drawings 5 1 NCU 1760 dimension drawing NCU 1760 44 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 48: ...Installation 6 4 Mounting the NCU without spacers NCU 1760 48 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 150: ...Connectable components 11 3 PP 72 48D PN 2 2A PN NCU 1760 150 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 154: ...Spare parts accessories 12 2 SD card NCU 1760 154 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 156: ...Safety symbols NCU 1760 156 Equipment Manual 02 2020 A5E45627861B AB ...
Страница 160: ...Appendix A 2 Documentation overview SINUMERIK ONE NCU 1760 160 Equipment Manual 02 2020 A5E45627861B AB ...