PROFIBUS DP Communication
8.5 DP slave I/O Module PP72/48
Manual
252
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
8.5.4
Setting the I/O addresses
When the dialog box is closed DP slave PP72/48 is inserted into the DP master system and
the detail view of DP slave PP72/48 is displayed in the station window. Select one of the
modules listed under DP slave PP72/48 (PP input/output module) from the hardware catalog
and insert it in slot 1 of the detail view.
The I/O addresses are assigned by "HW Config" automatically and should be changed
taking into account the following supplementary conditions:
●
I/O address area of NC
The 256-271 I/O addresses should not be assigned for compatibility reasons and for
future system extensions.
●
Selective access to inputs/outputs via the PLC
The PLC cannot access the individual I/Os directly for I/O address >256. The input/output
data must first be copied into internal flags of the PLC with the system functions SFC14
and 15.
It is therefore recommended for the reasons given above, that the I/O addresses should be
assigned in the 0-255 range.
The dialog box offers the following configurations to choose from:
1.
O/I 6/9 A222 E212121
2.
O/I 6/9 A411 E212121
3.
O/I 6/9 A42 E41
For DP slave PP72/48, select the 1st configuration and click OK to confirm the dialog box.
Содержание SINUMERIK 840Di sl
Страница 118: ...Configuration 3 3 Connection overview Manual 118 Commissioning Manual 05 2008 6FC5397 4CP10 4BA0 ...
Страница 148: ...Power On and Power Up 5 7 License management Manual 148 Commissioning Manual 05 2008 6FC5397 4CP10 4BA0 ...
Страница 186: ...PLC commissioning 6 8 Load configuration in PG PLC STEP 7 Manual 186 Commissioning Manual 05 2008 6FC5397 4CP10 4BA0 ...
Страница 344: ...Drive commissioning SINAMICS 9 5 Basic principles Manual 344 Commissioning Manual 05 2008 6FC5397 4CP10 4BA0 ...
Страница 624: ...Glossary Manual 624 Commissioning Manual 05 2008 6FC5397 4CP10 4BA0 ...