Wiring analog inputs/outputs
Procedure:
1. Strip cable for analog signals.
2. Secure the stripped connection piece of the cable with the shield connection clamp.
NOTICE
Shield contact
If the analog inputs/outputs are wired, a shielded lead must be used. The shield must be
supported.
X3 pin assignment
Table 7-92
Pin assignment (standard)
Pin
Signal name
Signal type
Meaning
1
CO1
O
Channel 1 current output for PT100
2
CI1
I
Channel 1 current input for PT100
3
AI1+
I
Channel 1 analog input +
4
AI1-
I
Channel 1 analog input -
5
CO2
O
Channel 2 current output for PT100
6
CI2
I
Channel 2 current input for PT100
7
AI2+
I
Channel 2 analog input +
8
AI2-
I
Channel 2 analog input -
9
AO3+
O
Channel 3 current and voltage
10
AO3-
O
Channel 3 current and voltage output -
11
AO4+
O
Channel 4 current and voltage
12
AO4-
O
Channel 4 current and voltage output -
The analog signal to be measured is connected to the terminals AI 1+/- and AI 2+/-. AI stands for "Analog
Input". The CO "Current Output" and CI "Current Input" terminals supply the constant current for the 4-
wire measurement of PT100 elements.
Analog inputs
The module has two analog inputs. These can optionally be assigned parameters as voltage,
current or PT100 input.
Note
The analog inputs are only enabled following the parameter assignment.
Cycle time of the analog value accumulation: 20 ms per channel
Connectable components
7.7 PP 72/48D 2/2A PN
PPU
200
Manual, 01/2014, 6FC5397-2DP40-3BA3
Содержание SINUMERIK 828D PPU Series
Страница 12: ......
Страница 34: ......
Страница 42: ......
Страница 52: ......
Страница 92: ......
Страница 150: ... r r r Connectable components 7 4 Electronic handwheel PPU 150 Manual 01 2014 6FC5397 2DP40 3BA3 ...
Страница 224: ......
Страница 226: ......
Страница 240: ......
Страница 244: ......