background image

A6V11387248_en--_a 

Smart Infrastructure

2020-08-28

Building Products

Sinorix™

RACW-140L X, RACW-140L EX4, RACW-140L EX5  

IG-01, IG-55, IG-100, IG-541 

Wall-mounted rack module for extinguishant cylinders

●  Main module for 1 to 5 cylinders 
●  Extension module for 4 or 5 cylinders 
●  Cylinder arrangement on 1 or 2 rows 
●  Compatibility with 140 l extinguishant cylinders 

Product codes:  
RACW-140L 1 - S54476-B615-A1 

RACW-140L 2 - S54476-B615-A2 

RACW-140L 3 - S54476-B615-A3 

RACW-140L 4 - S54476-B615-A4 

RACW-140L 5 - S54476-B615-A5 

RACW-140L EX4 - S54476-B616-A4 

RACW-140L EX5 - S54476-B616-A5 

Содержание Sinorix RACW-140L X

Страница 1: ...ishant cylinders Main module for 1 to 5 cylinders Extension module for 4 or 5 cylinders Cylinder arrangement on 1 or 2 rows Compatibility with 140 l extinguishant cylinders Product codes RACW 140L 1 S54476 B615 A1 RACW 140L 2 S54476 B615 A2 RACW 140L 3 S54476 B615 A3 RACW 140L 4 S54476 B615 A4 RACW 140L 5 S54476 B615 A5 RACW 140L EX4 S54476 B616 A4 RACW 140L EX5 S54476 B616 A5 ...

Страница 2: ...or 1 to 3 cylinders 3 for 4 to 5 cylinders 3 Type of modules Module number Product code Reference 1 S54476 B615 A1 RACW 140L 1 Main module for wall mounted rack 1 cylinder 2 S54476 B615 A2 RACW 140L 2 Main module for wall mounted rack 2 cylinders 3 S54476 B615 A3 RACW 140L 3 Main module for wall mounted rack 3 cylinders 4 S54476 B615 A4 RACW 140L 4 Main module for wall mounted rack 4 cylinders 5 S...

Страница 3: ... 8 4 144 402 12 4 4 4 13 12 9 4 517 402 13 5 4 4 14 13 9 4 890 402 14 5 4 5 15 14 9 5 263 402 15 5 5 5 16 15 9 5 636 402 List of modules for a 2 row arrangement 3 to 30 cylinders Required space for installation including cylinders Number of cylinders on 2 rows Required module number Number of threaded rods 2 rows S54476 B618 A2 Number of cylinder clamps S54476 B617 A1 Number of DN50 S54476 B609 A1...

Страница 4: ...roduct may only be installed by Siemens authorized specialized installers with experience in the design installation and maintenance of automatic extinguishing systems During installation it must be ensured that this product is installed in compliance with the accident prevention regulations and national regulations in force this product is used as intended any danger is avoided Siemens requiremen...

Страница 5: ...ack should only be installed on a reinforced concrete wall If the wall is made of bricks or plasterboard or if there is any doubt about the wall structure it is recommended to use a free standing rack Maintenance Storage Store in its original packaging protected from shocks Store in a clean and dry location protected from bad weather Inspection Check that the product is in a good condition Check t...

Страница 6: ...Channel Sikla 41 x 41 x 2 5 mm Weight RACW 140L 1 RACW 140L 2 RACW 140L 3 RACW 140L 4 RACW 140L 5 RACW 140L EX4 RACW 140L EX5 1 100 kg 4 410 kg 5 290 kg 6 230 kg 7 100 kg 6 130 kg 7 000 kg Cylinder volume 140 l Certifications and compliances Surface DIN EN ISO 1461 t Zn o Dimensions Dimensions in mm Reference A RACW 140L 1 414 RACW 140L 2 787 RACW 140L 3 1 160 RACW 140L 4 1 533 RACW 140L 5 1 906 R...

Страница 7: ...zerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2019 Technical specifications and availability subject to change without notice Document ID A6V11387248_en _a Edition 2020 08 28 ...

Отзывы: