PROFIdrive telegrams
● Standard telegrams
The standard telegrams are structured in accordance with the PROFIdrive profile. The drive-
internal process data links are set up automatically in the STARTER in accordance with
the telegram number setting.
The converter List Manual contains the standard telegrams in the following function
diagrams:
– 2415 PROFIdrive - Standard telegrams and process data 1
– 2416 PROFIdrive - Standard telegrams and process data 2
● Manufacturer-specific telegrams
The manufacturer-specific telegrams are structured in accordance with internal company
specifications. The drive-internal process data links are set up automatically in the
STARTER in accordance with the telegram number setting.
The converter List Manual contains the manufacturer-specific telegrams (SIEMENS
telegrams) in the following function diagrams:
– 2419 PROFIdrive - Manufacturer-specific telegrams and process data 1
– 2420 PROFIdrive - Manufacturer-specific telegrams and process data 2
– 2421 PROFIdrive - Manufacturer-specific telegrams and process data 3
– 2422 PROFIdrive - Manufacturer-specific telegrams and process data 4
● Supplementary telegrams
The converter List Manual contains the supplementary telegrams in the following function
diagrams:
– 2423 PROFIdrive ‑ manufacturer-specific/free telegrams and process data
● Free telegrams (p0922 = 999)
The converter List Manual contains the free telegrams in the following function diagrams:
– 2468 PROFIdrive – IF1 receive telegram, free interconnection via BICO (p0922 = 999)
– 2470 PROFIdrive – IF1 send telegram, free interconnection via BICO (p0922 = 999)
The receive and send data can be freely connected using BICO technology.
SERVO, TM41
VECTOR
CU_S
A_INF, B_INF,
S_INF
TB30, TM31,
TM15DI_DO,
TM120,
TM150
ENCODER
Receive process data
DWORD connec‐
tor output
r2060[0 ... 18]
r2060[0 ... 30]
-
-
-
r2060[0 ... 2]
WORD connec‐
tor output
r2050[0 ... 19]
r2050[0 ... 31]
r2050[0 ... 19]
r2050[0 ... 9]
r2050[0 ... 4] r2050[0 ... 3]
Binector output
r2090.0 ... 15
r2091.0 ... 15
r2092.0 ... 15
r2093.0 ... 15
r2090.0 ... 15
r2091.0 ... 15
r2090.0 ... 15
r2091.0 ... 15
r2092.0 ... 15
r2093.0 ... 15
Communication
A.1 Communication
Industrial Security
Configuration Manual, 08/2017, A5E36912609A
87
Содержание SINAMICS
Страница 6: ...Table of contents Industrial Security 6 Configuration Manual 08 2017 A5E36912609A ...
Страница 8: ...Introduction Industrial Security 8 Configuration Manual 08 2017 A5E36912609A ...
Страница 18: ...Industrial Security 3 4 Security management Industrial Security 18 Configuration Manual 08 2017 A5E36912609A ...
Страница 222: ...Communication A 1 Communication Industrial Security 222 Configuration Manual 08 2017 A5E36912609A ...
Страница 224: ...Service Support Industrial Security 224 Configuration Manual 08 2017 A5E36912609A ...