Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
155
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P0927
Parameter changeable
via
-
1111 bin U, T
-
-
U16
2
Specifies the interfaces which can be used to change parameters. This parameter allows the user to easily
protect the inverter from unauthorized modification of parameters.
Annotation: P0927 is not password protected.
Bit
Signal name
1 signal
0 signal
00
Not used
Yes
No
01
Not used
Yes
No
02
USS on RS232 (reserved)
Yes
No
03
USS on RS485
Yes
No
Example:
Default: All bits are set.
The default setting allows parameters to be changed via any interface.
r0944
Total number of
messages
-
-
-
-
-
U16
3
Displays the total number of messages available.
r0947[0...63] CO: Last fault code
-
-
-
-
-
U16
2
Displays fault history.
Index:
[0]
Recent fault trip --, fault 1
[1]
Recent fault trip --, fault 2
...
...
[7]
Recent fault trip --, fault 8
[8]
Recent fault trip -1, fault 1
Note:
See Chapter "Fault and warning codes (Page 233)".
r0948[0...63]
Fault time
-
-
-
-
-
U32
3
Time stamp to indicate when a fault has occurred.
P0969 (system run time counter) is the possible source of the time stamp.
Index:
[0]
Recent fault trip --, fault time 1
[1]
Recent fault trip --, fault time 2
...
...
[7]
Recent fault trip --, fault time 8
[8]
Recent fault trip -1, fault time 1
r0949[0...63] CO: Fault value
-
-
-
-
-
U32
3
Displays inverter fault values. It is for service purposes and indicates the type of fault reported.
The values are not documented. They are listed in the code where faults are reported.
Index:
[0]
Recent fault trip --, fault value 1
[1]
Recent fault trip --, fault value 2
...
...
[7]
Recent fault trip --, fault value 8
[8]
Recent fault trip -1, fault value 1
P0952
Total number of trips
0 - 65535 0
T
-
-
U16
3
Displays number of trips stored in r0947.
Dependency: Setting 0 resets fault history (changing to 0 also resets r0948 - fault time).
r0964[0...6]
Firmware version data
-
-
-
-
-
U16
3
Firmware version data.
Index:
[0]
Company (Siemens = 42)
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...