Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
147
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
Note:
Where:
•
P denotes Pulse
•
FWD denotes FORWARD
•
REV denotes REVERSE
When any of the control functions are selected using P0727, the setting for the digital inputs (P0701 -
P0704) are redefined as follows:
Settings of P0701
- P0704
P0727 = 0 (Siemens
Standard Control)
P0727 = 1 (2-
wire Control)
P0727 = 2 (3-
wire Control)
P0727 = 3 (3-
wire Control)
= 1 (P0840)
ON / OFF1
ON_FWD
STOP
ON_PULSE
= 2 (P0842)
ON_REV / OFF1
ON_REV
FWDP
OFF1 / HOLD
= 12 (P1113)
REV
REV
REVP
REV
To use the 2 / 3-wire control, the sources for ON / OFF1 (P0840), ON_REV / OFF1 (P0842) and REV
(P1113) corresponding to the redefined values have to be set accordingly.
Regarding the use of fixed frequencies see P1000 and P1001.
r0730
Number of digital outputs -
-
-
-
-
U16
3
Displays number of digital outputs.
P0731[0...2] BI: Function of digital
output 1
-
52.3
U, T
-
CDS
U32 /
Bin
2
Defines source of digital output 1.
Notice:
An inverse logic can be realized by inverting the digital outputs in P0748.
Note:
Output of fault bit 52.3 is inverted on digital output. Therefore, with P0748 = 0, the digital output is set to
low when a fault is triggered, and when there is no fault, it is set to high.
Monitor functions ==> see r0052, r0053
Motor holding brake ==> see P1215
DC-Brake ==> see P1232, P1233
P0732[0...2] BI: Function of digital
output 2
-
52.7
U, T
-
CDS
U32 /
Bin
2
Defines source of digital output 2.
r0747.0...1
CO / BO: State of digital
outputs
-
-
-
-
-
U16
3
Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Bit
Signal name
1 signal
0 signal
00
Digital output 1 energized
Yes
No
01
Digital output 2 energized
Yes
No
Dependency: Bit = 0 signal: Contacts open
Bit = 1 signal: Contacts closed
P0748
Invert digital outputs
-
0000 bin U, T
-
-
U16
3
Defines high and low states of digital output for a given function.
Bit
Signal name
1 signal
0 signal
00
Invert digital output 1
Yes
No
01
Invert digital output 2
Yes
No
r0750
Number of analog inputs -
-
-
-
-
U16
3
Displays number of analog inputs available.
r0751.0...9
CO / BO: Status word of
analog input
-
-
-
-
-
U16
3
Displays status of analog input.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...