Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
249
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
r1024
CO: Actual fixed fre-
quency [Hz]
-
-
-
-
-
Float 3
Displays sum total of selected fixed frequencies.
r1025.0
BO: Fixed frequency
status
-
-
-
-
-
U16
3
Displays the status of fixed frequencies.
Bit
Signal name
1 signal
0 signal
00
Status of FF
Yes
No
P1031[0...2]
MOP mode
0 - 3
1
U, T
-
DDS
U16
2
MOP mode specification.
Bit
Signal name
1 signal
0 signal
00
Setpoint store active
Yes
No
01
No On-state for MOP necessary
Yes
No
Note:
Defines the operation mode of the motorized potentiometer. See P1040.
P1032
Inhibit reverse direction
of MOP
0 - 1
1
T
-
-
U16
2
Inhibits reverse setpoint selection of the MOP.
0
Reverse direction is allowed
1
Reverse direction inhibited
Note:
It is possible to change motor direction using the motor potentiometer setpoint (increase/decrease fre-
quency).
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
frequency).
If P1032 = 1 and P1000 = 1 or 1X, then reverse motor direction will be inhibited.
P1035[0...2]
BI: Enable MOP (UP-
command)
0 - 4294967295 19.13
T
-
CDS
U32
3
Defines source for motor potentiometer setpoint increase frequency.
Setting:
722.0
Digital input 1 (requires P0701 to be set to 99, BICO)
722.1
Digital input 2 (requires P0702 to be set to 99, BICO)
722.2
Digital input 3 (requires P0703 to be set to 99, BICO)
Notice:
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator accelerates with the rate of
P1047.
P1036[0...2]
BI: Enable MOP
(DOWN-command)
0 - 4294967295 19.14
T
-
CDS
U32
3
Defines source for motor potentiometer setpoint decrease frequency.
Setting:
See P1035
Notice:
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator decelerates with the rate of
P1048.
Содержание SINAMICS V20 Inverter
Страница 1: ...SINAMICS V20 Converter ...
Страница 2: ......
Страница 8: ...Preface SINAMICS V20 Converter 6 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 346: ...Faults and alarms 9 2 Alarms SINAMICS V20 Converter 344 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 358: ...Technical specifications SINAMICS V20 Converter 356 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 426: ......