![Siemens SINAMICS SM150 Скачать руководство пользователя страница 68](http://html.mh-extra.com/html/siemens/sinamics-sm150/sinamics-sm150_operating-and-installation-instructions_378231068.webp)
11.Check if the circuit-breaker remains closed.
12.Release the mushroom pushbutton.
13.Make sure that the motor does not start.
14.Re-activate the acknowledge button.
15.Log the test (see sections "Cyclic function test log" and "Acceptance certificate").
3.6.11.4
Cyclic function test
The processes described in the chapter "Commissioning" in sections "Checking the voltage
monitoring relay -A11" and "Function test "Safe Torque Off"" must be repeated within a time
interval of six months. This satisfies the requirements for timely error detection.
3.6.11.5
Acceptance test and log
General
To verify the correct operation of the activated Safety Integrated functions (SI functions), the
machine manufacturer
1)
must perform an acceptance test of the activated SI functions on the
machine.
1)
In complex systems the machine manufacturer can be the system integrator.
Authorized persons
The test of each SI function must be performed by an authorized person. The authorized person
records and signs the test in the acceptance certificate.
Authorized in this sense refers to a person who has the necessary technical training and
knowledge of the safety functions and is authorized by the machine manufacturer to carry out
the test.
Documentation
To ensure clear documentation of commissioning, you must fill out the acceptance certificate
immediately (see section "Acceptance certificate (Page 70)") and store it in the machine's
logbook.
You must complete this report for each "Safe Torque Off" option of the plant/system.
Note
If you change the parameter of the SI functions, perform a new acceptance test. Enter the
acceptance test results in the acceptance certificate.
Description
3.6 Description of options
SINAMICS SM150 6SL3845-7NN46-7AA0
68
Operating Instructions 04/2017
Содержание SINAMICS SM150
Страница 2: ...20 04 2017 13 53 V27 00 ...
Страница 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Страница 16: ...Introduction 1 1 About these instructions SINAMICS SM150 6SL3845 7NN46 7AA0 16 Operating Instructions 04 2017 ...
Страница 82: ...Description 3 6 Description of options SINAMICS SM150 6SL3845 7NN46 7AA0 82 Operating Instructions 04 2017 ...
Страница 106: ...Installation 5 9 Connecting the water circuits SINAMICS SM150 6SL3845 7NN46 7AA0 106 Operating Instructions 04 2017 ...
Страница 120: ...Electrical connection 6 5 Connection SINAMICS SM150 6SL3845 7NN46 7AA0 120 Operating Instructions 04 2017 ...
Страница 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Страница 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Страница 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Страница 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Страница 217: ......