6.5.5
Connect the power cable to the motor and the supply system
When connecting the cables, observe all the conditions regarding conductor protection. Do not
exceed the permitted cable lengths between the converter output and motor. The distance
between the motor cable and the signal cable should be at least 20 cm. Do not lay grid-side and
motor supply cables in parallel to each other.
The positions of the connections are shown in the layout diagrams. Detailed wiring notes for the
converter are contained in the circuit manual of the converter.
Select the appropriate cable depending on the following conditions:
● Routing conditions
● Accumulation of cables
● Ambient temperature
● Bending radii
● Output voltage
Observe the connection capabilities on the converter and on the motor terminal box.
Procedure
1. Open the cabinet.
2. Remove or slide away the cover plate for the motor cable penetration.
Note
To route the power cables from above into the cabinet, remove the cover plate at the top of the
cabinet.
Cable fire caused by high transition resistances
Cables connected to the connection point that are not in compliance with the applicable
regulations represent a high electrical transition resistance that can cause thermal damage
(fire) during operation.
● Tighten the screws with the required torque.
Electrical connection
6.5 Connection
SINAMICS SM150 6SL3845-2NN41-8AD0
Operating Instructions Rev.201908010908 EXAMPLE
93
Содержание Sinamics SM150 6SL3845-2NN41-8AD0
Страница 2: ...01 08 2019 09 08 V32 00 ...
Страница 98: ...Start up SINAMICS SM150 6SL3845 2NN41 8AD0 98 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 172: ...Spare parts SINAMICS SM150 6SL3845 2NN41 8AD0 172 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 176: ...Service Support SINAMICS SM150 6SL3845 2NN41 8AD0 176 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 187: ......
Страница 190: ......
Страница 192: ......