Table 6-2
Cable cross-sections
Object
Cross-section
Comments
Power cable
Max. 240 mm
2
Max. six parallel power cables
Cabinet protective conductor
Max. 120 mm²
-
See also
6.5
Connection
6.5.1
Manually unlocking power-unit doors
To ensure operator protection, the drive is equipped with an electromechanical door
interlocking system. The doors cannot be opened until the make-proof grounding switch has
been closed. In the event of a complete voltage failure including failure of the auxiliary voltage,
the doors cannot be released via the grounding switch.
Because the drive is not yet connected, the doors are locked electromechanically. In order to
facilitate assembly and installation of the drive, the doors can be opened manually.
See also
6.5.2
Connecting ground
DANGER
Danger to life as a result of insufficient grounding
The drive must be grounded to ensure that it operates safely and reliably. If the drive is
operated with insufficient grounding, then the protection and monitoring functions can fail.
Death, serious injury, or material damage will result.
● To ensure the correct functioning of the protection and monitoring equipment, ground the
device.
Each cabinet has a grounding lug for grounding the components installed in the cabinet. It is
located at the bottom of the cabinet. Connect the cabinets securely to the plant grounding
system via these grounding lugs.
Electrical connection
6.5 Connection
SINAMICS SM150 6SL3845-2NN41-8AD0
Operating Instructions Rev.201908010908 EXAMPLE
91
Содержание Sinamics SM150 6SL3845-2NN41-8AD0
Страница 2: ...01 08 2019 09 08 V32 00 ...
Страница 98: ...Start up SINAMICS SM150 6SL3845 2NN41 8AD0 98 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 172: ...Spare parts SINAMICS SM150 6SL3845 2NN41 8AD0 172 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 176: ...Service Support SINAMICS SM150 6SL3845 2NN41 8AD0 176 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 187: ......
Страница 190: ......
Страница 192: ......