9.5.11
Replacing the precharging transformer
WARNING
Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
● Follow "the five safety rules (Page 15)".
● Before replacing the precharging transformer, open the safety disconnector for the 400 V
supply.
● Lift the transformer carefully because it is heavy (> 45 kg).
Removing the precharging transformer
1. Detach the high-voltage cables
①
.
2. Detach the 400 V connecting cables
②
.
3. Detach the grounding cable
③
.
4. Remove the fixing screws
④
at the front and rear on the base brackets.
5. Remove the transformer.
Figure 9-13
Replacing the precharging transformer
Maintenance
9.5 Repair
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE