To close the make-proof grounding switch, proceed as follows:
1. Take the socket wrench found in the tool set.
2. Turn the socket wrench in the clockwise direction.
The contacts are closed and the DC-link voltage is grounded.
3. Withdraw the socket wrench.
Figure 9-2
Make-proof-grounding switch closed
9.3
Opening the doors
The drive is equipped with a door interlocking system. Depending on the design, this is an
electromechanical door interlocking system or optionally a safety locking system.
The door of the closed-loop control cabinet is not electromechanically interlocked. For this
reason, it can also be opened during operation.
9.3.1
Opening the power unit doors for maintenance work
The doors can only be opened under the following conditions:
● The DC-link voltage is below a threshold value of 60 V.
● The circuit-breaker is open.
● The make-proof grounding switch is closed. The make-proof grounding switch is enabled by
the software.
● With synchronous motors, the field contactor must return the external enable signal at the
input with the status "OFF".
Maintenance
9.3 Opening the doors
SINAMICS SM150 6SL3810-7NN38-0AA1
Operating Instructions Rev.201910281406 EXAMPLE
145
Содержание SINAMICS SM150 6SL3810-7NN38-0AA1
Страница 2: ...28 10 2019 14 06 V32 00 ...
Страница 12: ...Table of contents SINAMICS SM150 6SL3810 7NN38 0AA1 12 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 106: ...Start up SINAMICS SM150 6SL3810 7NN38 0AA1 106 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 168: ...Spare parts SINAMICS SM150 6SL3810 7NN38 0AA1 168 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 172: ...Service Support SINAMICS SM150 6SL3810 7NN38 0AA1 172 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 183: ......
Страница 186: ......
Страница 188: ......