![Siemens SINAMICS SH150 Скачать руководство пользователя страница 105](http://html.mh-extra.com/html/siemens/sinamics-sh150/sinamics-sh150_operating-instructions-and-installation-instructions_378227105.webp)
9.7.7
Replacing a power cell
Safety instructions for replacing a power cell
WARNING
Danger to life as a result of defective discharge resistors
High voltages may occur at the DC link capacitors of the power cells due to defective
discharge resistors. Touching live components can result in death or serious injury.
● The five safety rules (Page 13) must be observed.
● Before replacing a power cell, ensure the following:
– The power cell is grounded at the input and output.
– There is no voltage at the power cells.
Check that the power cells are in a no-voltage condition at the terminals of the power
cell as well as the connections of the capacitor bank.
CAUTION
Risk of injury caused by incorrectly removing a power cell
Each power cell comprises two mechanical units, which can be separated:
● IGBT module weighing about 12 kg
● The capacitor bank with a weight of approx. 44 kg
Removing the power cells incorrectly can lead to serious injury and material damage.
● When installing and removing the power cell, do not position yourself below the individual
units.
NOTICE
Malfunction when replacing individual capacitors
It is not permissible to individually replace capacitors in the capacitor bank. If this is not
observed, this can result in malfunction.
● Only replace the complete capacitor bank.
NOTICE
Damage to components when using impact screwdrivers
Even with the correct torque, components can be damaged when using an impact
screwdriver. This can cause the device to fail.
● Never use an impact screwdriver.
Maintenance
9.7 Repair
SINAMICS SH150 6SL3805
Operating Instructions 05/2020
105
Содержание SINAMICS SH150
Страница 2: ...19 06 2020 09 42 V14 00 ...
Страница 12: ...Introduction 1 1 About these instructions SINAMICS SH150 6SL3805 12 Operating Instructions 05 2020 ...
Страница 42: ...Description 3 9 Interfaces SINAMICS SH150 6SL3805 42 Operating Instructions 05 2020 ...
Страница 56: ...Preparations for use 4 5 Storage SINAMICS SH150 6SL3805 56 Operating Instructions 05 2020 ...
Страница 116: ...Spare parts SINAMICS SH150 6SL3805 116 Operating Instructions 05 2020 ...
Страница 120: ...Service Support SINAMICS SH150 6SL3805 120 Operating Instructions 05 2020 ...
Страница 124: ...Technical data and drawings B 2 Environmental conditions SINAMICS SH150 6SL3805 124 Operating Instructions 05 2020 ...
Страница 126: ...Quality documents SINAMICS SH150 6SL3805 126 Operating Instructions 05 2020 ...
Страница 128: ...Additional documents SINAMICS SH150 6SL3805 128 Operating Instructions 05 2020 ...
Страница 131: ......
Страница 132: ...Further Information www siemens com LDA Siemens AG Large Drives Applications Vogelweiherstr 1 15 90441 NÜRNBERG GERMANY ...