Additional system components
7.3 Sensor Module Cabinet-Mounted SMC30
SINAMICS DCM DC Converter
216
Operating Instructions, 12/2018, A5E34763375A
7.3.5
Meaning of the LEDs
Table 7- 17 Meaning of LEDs on the Sensor Module Cabinet SMC30
LED
Color
Status
Description, cause
Remedy
RDY
READY
-
Off
Electronics power supply is missing or outside permissible
tolerance range.
–
Green
Continuous
light
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
–
Orange
Continuous
light
DRIVE-CLiQ communication is being established.
–
Red
Continuous
light
At least one fault is present in this component.
Note:
The LED is activated irrespective of whether the
corresponding messages have been reconfigured.
Remedy and
acknowledge fault
Green/
red
Flashing
light 0.5 Hz
Firmware is being downloaded.
–
Green/
red
Flashing
light 2 Hz
Firmware download is complete. Wait for POWER ON.
Carry out a
POWER ON
Green/
orange
or
Red/
orange
Flashing
light
Component recognition via LED is activated (p0144).
Note:
Both options depend on the LED status when module
recognition is activated via p0144 = 1.
–
OUT > 5 V -
Off
Electronics power supply is missing or outside permissible
tolerance range.
Power supply
≤
5 V.
–
Orange
Continuous
light
Electronics power supply for encoder system available.
Power supply > 5 V.
Important:
Make sure that the connected encoder can be operated
with a 24 V power supply. If an encoder that is designed
for a 5 V supply is operated with a 24 V supply, this can
destroy the encoder electronics.
–