WARNING
Fire as a result of incorrectly dimensioned overcurrent protective devices in the DC link
connecting cable
Incorrectly dimensioned overcurrent protective devices can result in a fire and associated
smoke.
• Protect personnel and prevent fires by dimensioning the overcurrent protective devices in
the DC link connecting cable corresponding to the particular application.
• Comply with local installation regulations.
• Carefully check the overcurrent protective device to ensure that it functions perfectly, and
maintain it regularly in accordance with local installation regulations.
6.1.3
Interface description
2
1
①
Mounted DC link adapter 6SL3162-2BD00-0AA0, rated current: 43 A for a 100 mm wide compo‐
nent
②
Mounted DC link adapter 6SL3162-2BM01-0AA0 for a 150 mm wide component (for multi-tier
configurations)
Table 6-1
DC link connection (6SL3162-2BD00-0AA0 and 6SL3162-2BE00-0AA0)
Terminal
Function
Technical specifications
DCP
DC link positive
Supply voltage:
495 ... 720 V
DC
DCN
DC link negative
Accessories
6.1 DC link adapter
Booksize power units
74
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0