5.6.5
X24 24 V terminal adapter
Table 5-4
X24: 24 V terminal adapter
X24: 24 V terminal
adapter
Termi‐
nal
Function
Technical specifications
+
24 V power supply
24 V DC supply voltage
M
Ground
Electronics ground
Connectable cable cross-sec‐
tions
Flexible
with end sleeve, without plastic sleeve
with end sleeve, with plastic sleeve
AWG / kcmil
0.5 … 6 mm
2
0.5 … 6 mm
2
0.5 … 6 mm
2
20 ... 8
Stripped length
12 mm (0.47 inch)
Tool
Screwdriver 1.0 x 4.0 mm
Tightening torque
1.2 … 1.5 Nm (10.6 ... 13.3 lbf in)
The 24 V terminal adapter is included in the scope of supply.
5.6.6
Meaning of the LEDs
The Smart Line Module has 3 LEDs on the front cover. The upper LED (RDY 1) and the lower LED
(DC LINK) are active.
Table 5-5
Meaning of the LEDs on the Smart Line Module
Status
Description, cause
Remedy
LED RDY 1
DC LINK
Off
Off
The electronics power supply is missing or outside the
permissible tolerance range.
–
Green
--
1)
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
–
Orange
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
–
Red
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place. The DC link voltage is out‐
side the permissible tolerance range.
Check the line voltage.
Orange
Orange
DRIVE-CLiQ communication is being established.
–
Red
--
1)
This component has at least one fault.
Resolve and acknowledge the
fault.
Green/red
(0.5 Hz)
--
1)
Firmware is being downloaded.
–
Smart Line Modules
5.6 Interface description
Booksize power units
62