X1: Line connection
Termi‐
nal
Function
Technical specifications
Connectable cable cross-
sections
Flexible
With end sleeve, without plastic sleeve
With end sleeve, with plastic sleeve
AWG / kcmil
6 … 16 mm
2
6 … 16 mm
2
6 … 16 mm
2
10 ... 6
Stripped length
12 mm (0.47 inch)
Tool
Slotted screwdriver, 1.0 x 5.5 mm
Tightening torque
1.2 ... 1.5 Nm (10.6 lbf in)
1)
For ring cable lugs without insulation
The power plug is included in the scope of supply.
5.6.3
Protective conductor connection
①
②
Protective conductor connection at the power plug
Protective conductor connection at the housing
You can connect the protective conductor either at the power plug or at the housing.
The protective conductor connection at the housing is located next to the strain relief plate.
Protective conductor connection at the
housing
Technical specifications
Screw
M5
Ring/pipe-type cable lug
M5
Tool
Torx screwdriver T20
Tightening torque
3 Nm (26.6 lbf in)
For further information about protective connections, please refer to Chapter "Protective
connection and equipotential bonding (Page 138)".