Figure 8-4
Connection example: Overvoltage protection elements connected to components
8.8.5
Typical 24 V current consumption
The following table lists a typical current consumption to calculate the 24 V DC supply required
for the S220 components. The values serve as basis for the configuration.
Table 8-10
Current consumption 24 V DC
Component
Typical current consumption [A
DC
]
S220 Smart Line Modules
16 kW
0.70
24 kW
0.70
The typical current consumption values of S120 components are listed in Chapter "24 V DC
supply" of the SINAMICS S120 Equipment Manual Booksize Power Units (
support.industry.siemens.com/cs/ww/en/view/109781351
8.8.6
Selecting power supply units
The following devices meet the applicable requirements of EN 60204-1 and their use is
recommended.
Table 8-11
Recommended power supplies: SITOP Power modular
Rated output cur‐
rent [A]
Phases
Rated input voltage [V]
Operating voltage range [V]
Short-circuit current [A]
Article number
5
1 / 2
AC 120 … 230/230 … 500
85 … 264/176 … 550
Approx. 5.5 (powering up)
Typ. 15 for 25 ms (in opera‐
tion)
6EP1333-3BA00-8AC0
10
1 / 2
AC 120 … 230/230 … 500
85 … 264/176 … 550
Approx. 12 (powering up)
Typ. 30 for 25 ms (in opera‐
tion)
6EP1334-3BA00-8AB0
20
1 / 2
AC 120 / 230
85 … 132/176 … 264
Approx. 23 (powering up)
Typ. 60 for 25 ms (in opera‐
tion)
6EP1336-3BA00-8AA0
3
3 AC 230/400 … 288/500
320 … 550
6EP1436-3BA00-8AA0
40
1 / 2
AC 120/230
85 … 132/176 … 264
Approx. 46 (powering up)
Typ. 120 for 25 ms (in oper‐
ation)
6EP1337-3BA00-8AA0
3
3 AC 230/400 … 288/500
320 … 550
6EP1437-3BA00-8AA0
Control cabinet design and EMC booksize
8.8 24 V DC supply voltage
Booksize power units
130