Functions, monitoring and protective functions
9.5 Monitoring functions and protective functions
Enclosed Drives
706
Operating Instructions, 12/2018, A5E36652151A
Thermal motor model 1 (for permanent-magnet synchronous machines)
By deploying the thermal I
2
t motor model, the temperature rise of the motor windings as a
result of dynamic motor loads is also determined in addition to data acquired using a
temperature sensor.
The model motor temperature is indicated in r0632. It is calculated from the following values:
●
Absolute value of the actual current, unsmoothed (r0068[0])
●
Motor stall current (p0318)
●
I
2
t motor model thermal time constant (p0611)
●
Measured motor temperature (r0035) or motor ambient temperature (p0613, p0625) for
operation without temperature sensor
●
Motor temperature at rated load (p0605, for expansion p0627)
Commissioning the motor model
The thermal I
2
t motor model is activated via p0612.0 = 1, the expansions of the motor model
can additionally be activated via p0612.8 = 1.
Note
When commissioning the motor, thermal motor model 1 (p0612.0 = 1) including expansion
(p0612.8 = 1) is automatically activated.
Preconditions for automatic activation:
•
Use of a permanent magnet synchronous motor
•
There is no motor sensor
•
No (other) thermal motor model is activated
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......