Electrical installation
4.3 Important safety precautions
Enclosed Drives
62
Operating Instructions, 12/2018, A5E36652151A
4.3
Important safety precautions
WARNING
Failure to observe general safety instructions and residual risks
If the general safety instructions and remaining risks are not observed, accidents can occur
involving severe injuries or death.
•
Observe the general safety instructions.
•
When assessing the risk, take into account residual risks.
WARNING
Electric shock when using unsuitable fuses
If unsuitable fuses are used, an electric shock can cause severe injury or death.
•
Use only fuses recommended in the technical data.
•
Observe the necessary minimum short circuit current for the relevant fuse.
WARNING
Electric shock due to the residual charge of the DC link capacitors
Because of the DC-link capacitors, a hazardous voltage is still present for a period of time
after the power supply has been switched off.
If live components are touched then this can result in severe injury or death.
•
Open the unit only after the time specified on the warning label has elapsed.
•
Before starting work, check the absence of voltage by measuring all poles/phases, also
to ground.
NOTICE
Material damage resulting from switching on the device without forming the DC-link
capacitors
After a storage time exceeding two years, switching on the device without forming the
DC-link capacitors can damage it.
•
Before switching on the device, it should be formed after a storage time exceeding two
years, see "Maintenance and servicing".
Note
Touch protection
When the cabinet door is opened, cabinet units have touch protection in compliance with
DGUV Regulation 3 according to EN 50274.
These protective covers may need to be removed during installation and connection
procedures. Once work has been completed, the protective covers must be properly refitted.
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......