Functions, monitoring and protective functions
9.3 Drive functions
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
505
9.3
Drive functions
9.3.1
Motor data identification and automatic speed controller optimization
Description
Two motor identification options, which are based on each other, are available:
●
Motor identification with p1910 (standstill measurement)
●
Rotating measurement with p1960 (speed controller optimization)
These can be selected more easily via p1900.
●
p1900 = 2 selects the motor identification (motor not rotating).
●
p1900 = 1 also activates the rotating measurement; setting p1910 = 1 and p1960
depending on the current control type (p1300).
Parameter p1960 is set depending on p1300 as follows:
●
p1960 = 1, if p1300 = 20 or 22 (encoderless control)
●
p1960 = 2, if p1300 = 21 or 23 (control with encoder)
The measurements parameterized using p1900 are started in the following sequence after
the corresponding drive has been enabled:
●
Motor identification at standstill, after the measurement has been completed, the pulses
are inhibited and parameter p1910 is reset to 0.
●
Encoder adjustment - after the measurement has been completed, the pulses are
inhibited and parameter p1990 is reset to 0.
●
Rotating measurement - after the measurement has been completed, the pulses are
inhibited and parameter p1960 is reset to 0.
●
After all of the measurements activated using p1900 have been successfully completed,
p1900 itself is set to 0.
The measurement progress can be monitored using r0047.
Completion of the individual motor data identification runs can be read via parameters r3925
to r3928.
Note
Non-volatile saving
To set the new controller setting permanently, the data must be saved with p0977 or p0971
in a non-volatile memory.
Note
The motor data identification runs only influence the currently valid motor data set (MDS).
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......