Operation
6.6 Control via the operator panel
Enclosed Drives
310
Operating Instructions, 12/2018, A5E36652151A
6.6.7.1
LOCAL/REMOTE key
Activating the LOCAL mode: Press the LOCAL key
LOCAL mode: LED lights up
REMOTE mode: LED does not light up: the ON, OFF, JOG, direction reversal, faster, and
slower keys are not active.
Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Save LOCAL mode (factory setting: Yes)
●
Yes: The "LOCAL" or "REMOTE" operating mode is saved when the power supply is
switched off and restored when the power supply is switched back on.
●
No: "LOCAL" or "REMOTE" operating mode is not saved. "REMOTE" is active when the
supply voltage is switched back on.
OFF in REMOTE (factory setting: No)
●
Yes: The OFF key functions in REMOTE mode even if the drive is being controlled by
external sources (fieldbus, customer terminal block, NAMUR terminal block).
WARNING This function is not an EMERGENCY STOP function!
●
No: The OFF key only functions in LOCAL mode.
LOCAL/REMOTE also during operation (factory setting: No)
●
Yes: You can switch between LOCAL and REMOTE when the drive is switched on (motor
is running).
●
No: Before the system switches to LOCAL, a check is carried out to determine whether
the drive is in the operational status. If so, the system does not switch to local and
outputs the error message "Local mode during operation not possible". Before the system
switches to REMOTE, the drive is switched off and the setpoint is set to 0.
6.6.7.2
ON key / OFF key
ON key: Always active in LOCAL when the operator input inhibit is deactivated.
OFF key: In the factory setting, acts as OFF1 = ramp-down along the deceleration ramp
(p1121); when n = 0: Voltage disconnection (only if there is a main contactor)
The OFF key is effective in the LOCAL mode and when the "OFF in REMOTE" function is
active.
Settings: MENU – Commissioning / Service – AOP Settings – Control Settings
Red OFF key acts as: (factory setting: OFF1)
●
OFF1: Ramp-down along the down ramp (p1121)
●
OFF2: Immediate pulse inhibit, motor coasts down
●
OFF3: Ramp-down along the quick stop ramp (p1135)
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......